| Assessment Year | 2023 |
|---|---|
| Principal Product | Dump Body |
| NAICS | 336211: Motor Vehicle Body Manufacturing |
| SIC | 3713: Truck and Bus Bodies |
| Sales Range | $50 M to 100M |
| # of Employees | 176 |
| Plant Area |
177,000
ft2
|
| Annual Production | 2,000
units
|
| Production Hrs. Annual | 3,003
hrs
|
| Location (State) | Alabama |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $191,626 | 2,019,689 |
kWh
|
$0.095 |
| Electricity Demand | $51,713 | 7,194 |
kW-mo/yr
|
$7.19 |
| Electricity Fees | $14,771 | - |
|
- |
| Natural Gas | $129,407 | 9,924 |
MMBtu
|
$13.04 |
| TOTAL YEARLY COSTS | $387,517 | |||
| RECOMMENDED SAVINGS* | $46,587 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | - | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings |
|---|---|---|---|---|---|---|---|---|
| 01 | 2.4239: Eliminate or reduce compressed air usage | $5,807 | $1,000 |
$4,509
47,516
kWh
|
$966
-
kW-mo/yr
|
$332 | - | |
| 02 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $6,641 | $9,092 |
$5,467
57,604
kWh
|
$794
-
kW-mo/yr
|
$380 | - | |
| 03 | 2.2437: Recover waste heat from equipment | $4,098 | $8,397 | - | - | - |
$4,098
-
MMBtu
|
|
| 04 | 2.7135: Install occupancy sensors | $668 | $557 |
$630
6,642
kWh
|
- | $38 | - | |
| 05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $9,089 | $17,628 |
$6,539
68,903
kWh
|
$1,979
-
kW-mo/yr
|
$571 | - | |
| 06 | 2.7261: Install timers and/or thermostats | $1,836 | $1,190 |
$1,731
18,233
kWh
|
- | $105 | - | |
| 07 | 2.7231: Use radiant heater for spot heating | $18,030 | $20,167 | - | - | - |
$18,030
-
MMBtu
|
|
| 08 | 2.1121: Use insulation in furnaces to facilitate heating / cooling | $418 | $1,048 | - | - | - |
$418
-
MMBtu
|
|
| TOTAL RECOMMENDED | $46,587 | $59,079 |
$18,876
198,898
kWh
|
$3,739
-
kW-mo/yr
|
$1,426 |
$22,546
-
MMBtu
|
||
| TOTAL IMPLEMENTED | - | - | - | - | - | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs