Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $312,109 | 5,343,000 |
kWh
|
$0.058 |
Electricity Demand | $42,645 | 9,212 |
kW-mo/yr
|
$4.63 |
Electricity Fees | $42,482 | - |
|
- |
Natural Gas | $351,471 | 27,075 |
MMBtu
|
$12.98 |
TOTAL YEARLY COSTS | $748,707 | |||
RECOMMENDED SAVINGS* | $25,712 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $9,664 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings |
---|---|---|---|---|---|---|---|
01 | 2.3412: Use waste heat to produce steam to drive a steam turbine-generator | $13,660 | $51,749 |
$11,001
188,366
kWh
|
$1,198
-
kW-mo/yr
|
$1,461 | |
02 | 2.4231: Reduce the pressure of compressed air to the minimum required | $6,033 | $1,000 |
$4,193
71,792
kWh
|
$1,195
-
kW-mo/yr
|
$645 | |
03 | 2.7261: Install timers and/or thermostats | $2,954 | $1,360 |
$2,638
45,166
kWh
|
- | $316 | |
04 | 2.3212: Optimize plant power factor | $2,388 | $1,682 | - | - | $2,388 | |
05 | 2.7135: Install occupancy sensors | $677 | $901 |
$605
10,353
kWh
|
- | $72 | |
TOTAL RECOMMENDED | $25,712 | $56,692 |
$18,437
315,677
kWh
|
$2,393
-
kW-mo/yr
|
$4,882 | ||
TOTAL IMPLEMENTED | $9,664 | $3,261 |
$7,436
127,311
kWh
|
$1,195
-
kW-mo/yr
|
$1,033 |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs