Assessment Year | 2022 |
---|---|
Principal Product | yarn |
NAICS | 313110: Fiber, Yarn, and Thread Mills |
SIC | 2281: Yarn Spinning Mills |
Sales Range | $50 M to 100M |
# of Employees | 215 |
Plant Area |
468,888
ft2
|
Annual Production | 68,819,636
lb
|
Production Hrs. Annual | 8,760
hrs
|
Location (State) | Alabama |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $4,299,865 | 122,531,495 |
kWh
|
$0.035 |
Electricity Demand | $2,535,147 | 182,042 |
kW-mo/yr
|
$13.93 |
Electricity Fees | $(-414,308.0) | - |
|
- |
TOTAL YEARLY COSTS | $6,420,704 | |||
RECOMMENDED SAVINGS* | $107,036 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $93,015 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings |
---|---|---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $9,394 | $34,200 |
$6,282
178,984
kWh
|
$3,718
-
kW-mo/yr
|
$(-606.0) | |
02 | 2.7111: Reduce illumination to minimum necessary levels | $14,021 | $25,035 |
$8,796
250,589
kWh
|
$6,129
-
kW-mo/yr
|
$(-904.0) | |
03 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $9,508 | $4,445 |
$6,437
183,384
kWh
|
$3,684
-
kW-mo/yr
|
$(-613.0) | |
04 | 2.2691: Shut off cooling if cold outside air will cool process | $19,724 | $5,000 |
$20,997
598,340
kWh
|
- | $(-1,273.0) | |
05 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $8,015 | $30,617 |
$5,537
157,743
kWh
|
$2,995
-
kW-mo/yr
|
$(-517.0) | |
06 | 2.7224: Reduce space conditioning during non-working hours | $2,456 | $450 |
$2,614
74,482
kWh
|
- | $(-158.0) | |
07 | 2.3212: Optimize plant power factor | $43,918 | $57,938 | - | - | $43,918 | |
TOTAL RECOMMENDED | $107,036 | $157,685 |
$50,663
1,443,522
kWh
|
$16,526
-
kW-mo/yr
|
$39,847 | ||
TOTAL IMPLEMENTED | $93,015 | $132,650 |
$41,867
1,192,933
kWh
|
$10,397
-
kW-mo/yr
|
$40,751 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs