Assessment Year | 2022 |
---|---|
Principal Product | Office Furniture |
NAICS | 337214: Office Furniture (except Wood) Manufacturing |
SIC | 2522: Office Furniture, Except Wood |
Sales Range | greater than $500 M |
# of Employees | 800 |
Plant Area |
891,775
ft2
|
Annual Production | 3,300,000
lb
|
Production Hrs. Annual | 6,864
hrs
|
Location (State) | Alabama |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $1,154,493 | 19,148,400 |
kWh
|
$0.060 |
Electricity Demand | $657,702 | 45,547 |
kW-mo/yr
|
$14.44 |
Electricity Fees | $(-425,891.0) | - |
|
- |
Natural Gas | $663,691 | 87,815 |
MMBtu
|
$7.56 |
TOTAL YEARLY COSTS | $2,049,995 | |||
RECOMMENDED SAVINGS* | $133,642 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $34,145 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.7111: Reduce illumination to minimum necessary levels | $40,414 | $20,833 |
$34,141
566,280
kWh
|
$14,296
-
kW-mo/yr
|
$(-8,023.0) | - | |
02 | 2.7135: Install occupancy sensors | $314 | $705 |
$410
6,795
kWh
|
- | $(-96.0) | - | |
03 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $6,372 | $340 |
$5,179
85,907
kWh
|
$2,410
-
kW-mo/yr
|
$(-1,217.0) | - | |
04 | 2.4239: Eliminate or reduce compressed air usage | $10,267 | $1,000 |
$5,363
88,946
kWh
|
$8,058
-
kW-mo/yr
|
$(-3,154.0) | - | |
05 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $24,460 | $9,801 |
$31,056
515,115
kWh
|
$918
-
kW-mo/yr
|
$(-7,514.0) | - | |
06 | 2.7224: Reduce space conditioning during non-working hours | $3,313 | $459 | - | - | - |
$3,313
-
MMBtu
|
|
07 | 2.7231: Use radiant heater for spot heating | $48,502 | $37,450 | - | - | - |
$48,502
-
MMBtu
|
|
TOTAL RECOMMENDED | $133,642 | $70,588 |
$76,149
1,263,043
kWh
|
$25,682
-
kW-mo/yr
|
$(-20,004.0) |
$51,815
-
MMBtu
|
||
TOTAL IMPLEMENTED | $34,145 | $10,600 |
$36,235
601,022
kWh
|
$3,328
-
kW-mo/yr
|
$(-8,731.0) |
$3,313
-
MMBtu
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs