ITAC Assessment: UA0242
ITAC logo
ITAC Assessment: UA0242
Grant Funding Opportunity NOW OPEN
Up to $300k at 50% cost share for qualifying* projects.
Grant Funding Opportunity Open
Qualifying* small and medium-sized US manufacturers, that received an ITAC, Onsite Energy/CHP TAP, or qualified equivalent assessment since 2018 can now apply for grants for implementation of assessment recommendations at up to 50% of qualifying* project costs with a maximum of $300,000 per grant.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
Assessment Year 2021
Principal Product Rubber and Vinyl Flooring
NAICS 326199: All Other Plastics Product Manufacturing
SIC 3089: Plastics Products, Not Elsewhere Classified
Sales Range $50
M
to 100
M
# of Employees 200
Plant Area 250,000
ft2
Annual Production 20,000,000
lb
Production Hrs. Annual 6,000
hrs
Location (State) Alabama

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $838,893 11,935,200
kWh
Electricity Demand $636,248 50,791
kW-mo/yr
Electricity Fees $(-125,129.0) -
Natural Gas $129,701 50,362
MMBtu
TOTAL YEARLY COSTS $1,479,713
RECOMMENDED SAVINGS* $75,856 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $24,484

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Electricity Fees Savings Natural Gas Savings
01 2.4111: Utilize energy-efficient belts and other improved mechanisms $1,385 $59 $799
11,362
kWh
$714
-
kW-mo/yr
$(-128.0) -
02 2.3212: Optimize plant power factor $36,295 $6,449 - $39,660
-
kW-mo/yr
$(-3,365.0) -
03 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves $19,142 $9,682 $17,859
254,071
kWh
$3,057
-
kW-mo/yr
$(-1,774.0) -
04 2.7142: Utilize higher efficiency lamps and/or ballasts $3,957 $4,986 $3,184
45,294
kWh
$1,140
-
kW-mo/yr
$(-367.0) -
05 2.7231: Use radiant heater for spot heating $15,077 $22,703 - - - $15,077
-
MMBtu
TOTAL RECOMMENDED $75,856 $43,879 $21,842
310,727
kWh
$44,571
-
kW-mo/yr
$(-5,634.0) $15,077
-
MMBtu
TOTAL IMPLEMENTED $24,484 $14,727 $21,842
310,727
kWh
$4,911
-
kW-mo/yr
$(-2,269.0) -
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs