Assessment Year | 2021 |
---|---|
Principal Product | Automotive Structural Parts |
NAICS | 336390: Other Motor Vehicle Parts Manufacturing |
SIC | 3714: Motor Vehicle Parts and Accessories |
Sales Range | $10 M to 50M |
# of Employees | 139 |
Plant Area |
260,000
ft2
|
Annual Production | 415,000
units
|
Production Hrs. Annual | 5,880
hrs
|
Location (State) | Alabama |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $282,757 | 7,289,467 |
kWh
|
$0.039 |
Electricity Demand | $52,633 | 9,857 |
kW-mo/yr
|
$5.34 |
Electricity Fees | $28,353 | - |
|
- |
Natural Gas | $247,240 | 29,274 |
MMBtu
|
$8.45 |
TOTAL YEARLY COSTS | $610,983 | |||
RECOMMENDED SAVINGS* | $51,003 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $15,899 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.4231: Reduce the pressure of compressed air to the minimum required | $3,194 | $50 |
$2,114
54,531
kWh
|
$667
-
kW-mo/yr
|
$413 | - | |
02 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $2,993 | $2,238 |
$1,972
50,866
kWh
|
$634
-
kW-mo/yr
|
$387 | - | |
03 | 2.3212: Optimize plant power factor | $12,847 | $4,947 | - | - | $12,847 | - | |
04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $9,348 | $23,987 |
$6,308
162,748
kWh
|
$1,831
-
kW-mo/yr
|
$1,209 | - | |
05 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $364 | $51 |
$248
6,392
kWh
|
$69
-
kW-mo/yr
|
$47 | - | |
06 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $2,641 | $9,144 |
$1,794
46,289
kWh
|
$504
-
kW-mo/yr
|
$343 | - | |
07 | 2.7241: Install outside air damper / economizer on hvac unit | $18,822 | $2,500 |
$16,388
422,812
kWh
|
- | $2,434 | - | |
08 | 2.7231: Use radiant heater for spot heating | $794 | $709 | - | - | - |
$794
-
MMBtu
|
|
TOTAL RECOMMENDED | $51,003 | $43,626 |
$28,824
743,638
kWh
|
$3,705
-
kW-mo/yr
|
$17,680 |
$794
-
MMBtu
|
||
TOTAL IMPLEMENTED | $15,899 | $26,326 |
$10,642
274,537
kWh
|
$3,201
-
kW-mo/yr
|
$2,056 | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings |