| Assessment Year | 2020 |
|---|---|
| Principal Product | Rough sawn lumber |
| NAICS | 321113: Sawmills |
| SIC | 2421: Sawmills and Planing Mills, General |
| Sales Range | $5 M to 10M |
| # of Employees | 49 |
| Plant Area |
958,320
ft2
|
| Annual Production | 1,500
thousand feet
|
| Production Hrs. Annual | 2,340
hrs
|
| Location (State) | Alabama |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | ||
|---|---|---|---|---|---|
| Electricity Usage | $75,197 | 1,420,415 |
kWh
|
$0.053 | |
| Electricity Demand | $59,052 | 8,681 |
kW-mo/yr
|
$6.80 | |
| Electricity Fees | $24,241 | - |
|
- | |
| Wood | $65,315 | 38,478 |
MMBtu
|
$1.70 | |
| Waste Disposal Costs | |||||
| Water Usage | $6,518 | 1,384 |
Tgal
|
$4.71 | |
| TOTAL YEARLY COSTS | $230,323 | ||||
| RECOMMENDED SAVINGS* | $6,015 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
| IMPLEMENTED SAVINGS* | $2,793 | ||||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Wood Savings |
|---|---|---|---|---|---|---|---|---|
| 01 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $965 | $562 |
$462
8,727
kWh
|
$355
-
kW-mo/yr
|
$148 | - | |
| 02 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $1,828 | $1,395 |
$1,222
23,092
kWh
|
$326
-
kW-mo/yr
|
$280 | - | |
| 03 | 2.4231: Reduce the pressure of compressed air to the minimum required | $1,686 | $250 |
$989
18,680
kWh
|
$439
-
kW-mo/yr
|
$258 | - | |
| 04 | 2.2136: Install / repair insulation on steam lines | $1,536 | $3,806 | - | - | - |
$1,536
-
MMBtu
|
|
| TOTAL RECOMMENDED | $6,015 | $6,013 |
$2,673
50,499
kWh
|
$1,120
-
kW-mo/yr
|
$686 |
$1,536
-
MMBtu
|
||
| TOTAL IMPLEMENTED | $2,793 | $1,957 |
$1,684
31,819
kWh
|
$681
-
kW-mo/yr
|
$428 | - | ||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs