| Assessment Year | 2019 |
|---|---|
| Principal Product | Resilient Floor Covering |
| NAICS | 326199: All Other Plastics Product Manufacturing |
| SIC | 3996: Linoleum, Asphalted-Felt-Base, and Other Hard Surface Floor Coverings, Not Elsewhere Classified |
| Sales Range | $50 M to 100M |
| # of Employees | 125 |
| Plant Area |
185,000
ft2
|
| Annual Production | 100,000,000
units
|
| Production Hrs. Annual | 7,500
hrs
|
| Location (State) | Mississippi |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $895,386 | 17,294,508 |
kWh
|
$0.052 |
| Electricity Demand | $190,735 | 40,341 |
kW-mo/yr
|
$4.73 |
| Electricity Fees | $209,645 | - |
|
- |
| Natural Gas | $208,543 | 52,862 |
MMBtu
|
$3.95 |
| TOTAL YEARLY COSTS | $1,504,309 | |||
| RECOMMENDED SAVINGS* | $76,244 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $23,647 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings |
|---|---|---|---|---|---|---|---|---|
| 01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $22,484 | $31,859 |
$16,685
322,288
kWh
|
$2,162
-
kW-mo/yr
|
$3,637 | - | |
| 02 | 2.4231: Reduce the pressure of compressed air to the minimum required | $8,647 | $100 |
$6,316
121,997
kWh
|
$932
-
kW-mo/yr
|
$1,399 | - | |
| 03 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $16,098 | $4,895 |
$12,444
240,368
kWh
|
$1,050
-
kW-mo/yr
|
$2,604 | - | |
| 04 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $7,549 | $1,294 |
$4,658
89,986
kWh
|
$1,670
-
kW-mo/yr
|
$1,221 | - | |
| 05 | 2.2414: Use waste heat from hot flue gases to preheat | $6,067 | $30,000 | - | - | - |
$6,067
-
MMBtu
|
|
| 06 | 2.2614: Use cooling tower or economizer to replace chiller cooling | $15,399 | $4,370 |
$12,908
249,332
kWh
|
- | $2,491 | - | |
| TOTAL RECOMMENDED | $76,244 | $72,518 |
$53,011
1,023,971
kWh
|
$5,814
-
kW-mo/yr
|
$11,352 |
$6,067
-
MMBtu
|
||
| TOTAL IMPLEMENTED | $23,647 | $6,189 |
$17,102
330,354
kWh
|
$2,720
-
kW-mo/yr
|
$3,825 | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs