Assessment Year | 2019 |
---|---|
Principal Product | Resilient Floor Covering |
NAICS | 326199: All Other Plastics Product Manufacturing |
SIC | 3996: Linoleum, Asphalted-Felt-Base, and Other Hard Surface Floor Coverings, Not Elsewhere Classified |
Sales Range | $50 M to 100M |
# of Employees | 125 |
Plant Area |
185,000
ft2
|
Annual Production | 100,000,000
units
|
Production Hrs. Annual | 7,500
hrs
|
Location (State) | Mississippi |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $895,386 | 17,294,508 |
kWh
|
$0.052 |
Electricity Demand | $190,735 | 40,341 |
kW-mo/yr
|
$4.73 |
Electricity Fees | $209,645 | - |
|
- |
Natural Gas | $208,543 | 52,862 |
MMBtu
|
$3.95 |
TOTAL YEARLY COSTS | $1,504,309 | |||
RECOMMENDED SAVINGS* | $76,244 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $23,647 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $22,484 | $31,859 |
$16,685
322,288
kWh
|
$2,162
-
kW-mo/yr
|
$3,637 | - | |
02 | 2.4231: Reduce the pressure of compressed air to the minimum required | $8,647 | $100 |
$6,316
121,997
kWh
|
$932
-
kW-mo/yr
|
$1,399 | - | |
03 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $16,098 | $4,895 |
$12,444
240,368
kWh
|
$1,050
-
kW-mo/yr
|
$2,604 | - | |
04 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $7,549 | $1,294 |
$4,658
89,986
kWh
|
$1,670
-
kW-mo/yr
|
$1,221 | - | |
05 | 2.2414: Use waste heat from hot flue gases to preheat | $6,067 | $30,000 | - | - | - |
$6,067
-
MMBtu
|
|
06 | 2.2614: Use cooling tower or economizer to replace chiller cooling | $15,399 | $4,370 |
$12,908
249,332
kWh
|
- | $2,491 | - | |
TOTAL RECOMMENDED | $76,244 | $72,518 |
$53,011
1,023,971
kWh
|
$5,814
-
kW-mo/yr
|
$11,352 |
$6,067
-
MMBtu
|
||
TOTAL IMPLEMENTED | $23,647 | $6,189 |
$17,102
330,354
kWh
|
$2,720
-
kW-mo/yr
|
$3,825 | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs