Assessment Year | 2018 |
---|---|
Principal Product | Wastewater Treatment |
NAICS | 221320: Sewage Treatment Facilities |
SIC | 4952: Sewerage Systems |
Sales Range | $1 M to 5M |
# of Employees | 6 |
Plant Area |
522,720
ft2
|
Annual Production | 1,095,000
Tgal
|
Production Hrs. Annual | 8,760
hrs
|
Location (State) | Alabama |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $257,939 | 2,443,800 |
kWh
|
$0.11 |
Electricity Demand | $20,069 | 4,234 |
kW-mo/yr
|
$4.74 |
Electricity Fees | $(-7,427.0) | - |
|
- |
TOTAL YEARLY COSTS | $270,581 | |||
RECOMMENDED SAVINGS* | $38,128 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $36,001 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings |
---|---|---|---|---|---|---|---|
01 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $26,573 | $13,202 |
$24,982
236,684
kWh
|
$2,313
-
kW-mo/yr
|
$(-722.0) | |
02 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $2,127 | $1,410 |
$2,005
18,992
kWh
|
$185
-
kW-mo/yr
|
$(-63.0) | |
03 | 2.7261: Install timers and/or thermostats | $6,436 | $50 |
$6,628
62,795
kWh
|
- | $(-192.0) | |
04 | 2.7261: Install timers and/or thermostats | $2,992 | $180 |
$3,081
29,193
kWh
|
- | $(-89.0) | |
TOTAL RECOMMENDED | $38,128 | $14,842 |
$36,696
347,664
kWh
|
$2,498
-
kW-mo/yr
|
$(-1,066.0) | ||
TOTAL IMPLEMENTED | $36,001 | $13,432 |
$34,691
328,672
kWh
|
$2,313
-
kW-mo/yr
|
$(-1,003.0) |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs