| Assessment Year | 2018 |
|---|---|
| Principal Product | Nitrile Gloves |
| NAICS | 339113: Surgical Appliance and Supplies Manufacturing |
| SIC | 3069: Fabricated Rubber Products, Not Elsewhere Classified |
| Sales Range | $50 M to 100M |
| # of Employees | 170 |
| Plant Area |
150,000
ft2
|
| Annual Production | 200,000,000
units
|
| Production Hrs. Annual | 8,400
hrs
|
| Location (State) | Alabama |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | ||
|---|---|---|---|---|---|
| Electricity Usage | $260,587 | 4,763,000 |
kWh
|
$0.055 | |
| Electricity Demand | $52,666 | 10,920 |
kW-mo/yr
|
$4.82 | |
| Electricity Fees | $43,519 | - |
|
- | |
| Natural Gas | $528,422 | 126,954 |
MMBtu
|
$4.16 | |
| Waste Disposal Costs | |||||
| Water Usage | $19,713 | 433,347 |
Tgal
|
$0.045 | |
| TOTAL YEARLY COSTS | $904,907 | ||||
| RECOMMENDED SAVINGS* | $60,158 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
| IMPLEMENTED SAVINGS* | $21,237 | ||||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings |
|---|---|---|---|---|---|---|---|---|
| 01 | 2.2614: Use cooling tower or economizer to replace chiller cooling | $18,889 | $37,420 |
$15,683
286,657
kWh
|
$2,098
-
kW-mo/yr
|
$1,108 | - | |
| 02 | 2.6218: Turn off equipment when not in use | $15,914 | - | - | - | - |
$15,914
-
MMBtu
|
|
| 03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $14,060 | $34,939 |
$11,771
215,157
kWh
|
$1,464
-
kW-mo/yr
|
$825 | - | |
| 04 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $3,326 | $2,165 |
$2,924
54,454
kWh
|
$207
-
kW-mo/yr
|
$195 | - | |
| 05 | 2.4231: Reduce the pressure of compressed air to the minimum required | $2,391 | $150 |
$2,025
37,022
kWh
|
$226
-
kW-mo/yr
|
$140 | - | |
| 06 | 2.6212: Turn off equipment during breaks, reduce operating time | $1,997 | - |
$1,880
34,354
kWh
|
- | $117 | - | |
| 07 | 2.2437: Recover waste heat from equipment | $489 | $2,112 |
$412
7,532
kWh
|
$48
-
kW-mo/yr
|
$29 | - | |
| 08 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $3,092 | $2,256 |
$2,405
43,967
kWh
|
$506
-
kW-mo/yr
|
$181 | - | |
| TOTAL RECOMMENDED | $60,158 | $79,042 |
$37,100
679,143
kWh
|
$4,549
-
kW-mo/yr
|
$2,595 |
$15,914
-
MMBtu
|
||
| TOTAL IMPLEMENTED | $21,237 | $2,165 |
$4,804
88,808
kWh
|
$207
-
kW-mo/yr
|
$312 |
$15,914
-
MMBtu
|
||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs