Assessment Year | 2013 |
---|---|
Principal Product | walk-behind mower |
NAICS | 333112: Lawn and Garden Tractor and Home Lawn and Garden Equipment Manufacturing |
SIC | 3524: Lawn and Garden Tractors and Home Lawn and Garden Equipment |
Sales Range | $100 M to 500M |
# of Employees | 1,221 |
Plant Area |
900,000
ft2
|
Annual Production | 2,256,331
pieces
|
Production Hrs. Annual | 4,704
hrs
|
Location (State) | Mississippi |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $1,134,241 | 17,423,400 |
kWh
|
$0.065 |
Electricity Demand | $598,721 | 46,500 |
kW-mo/yr
|
$12.88 |
Electricity Fees | $(-252,866.0) | - |
|
- |
Natural Gas | $545,234 | 84,411 |
MMBtu
|
$6.46 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $175,948 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $12,301 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $109,678 | $164,833 |
$80,340
1,234,109
kWh
|
$50,463
-
kW-mo/yr
|
$(-21,125.0) | - | |
02 | 2.7122: Disconnect ballasts | $3,632 | $242 |
$2,658
40,824
kWh
|
$1,674
-
kW-mo/yr
|
$(-700.0) | - | |
03 | 2.7231: Use radiant heater for spot heating | $25,020 | $52,360 | - | - | $357 |
$24,663
-
MMBtu
|
|
04 | 2.3212: Optimize plant power factor | $19,434 | $14,980 | - |
$23,177
-
kW-mo/yr
|
$(-3,743.0) | - | |
05 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $12,301 | $5,000 |
$9,740
149,622
kWh
|
$4,930
-
kW-mo/yr
|
$(-2,369.0) | - | |
06 | 2.4231: Reduce the pressure of compressed air to the minimum required | $5,883 | $400 |
$3,971
61,003
kWh
|
$3,045
-
kW-mo/yr
|
$(-1,133.0) | - | |
TOTAL RECOMMENDED | $175,948 | $237,815 |
$96,709
1,485,558
kWh
|
$83,289
-
kW-mo/yr
|
$(-28,713.0) |
$24,663
-
MMBtu
|
||
TOTAL IMPLEMENTED | $12,301 | $5,000 |
$9,740
149,622
kWh
|
$4,930
-
kW-mo/yr
|
$(-2,369.0) | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs