| Assessment Year | 2012 |
|---|---|
| Principal Product | Dried Flowers |
| NAICS | 339999: All Other Miscellaneous Manufacturing |
| SIC | 3999: Manufacturing Industries, Not Elsewhere Classified |
| Sales Range | $5 M to 10M |
| # of Employees | 70 |
| Plant Area |
450,000
ft2
|
| Annual Production | 225,000
pieces
|
| Production Hrs. Annual | 2,295
hrs
|
| Location (State) | Alabama |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $90,068 | 1,069,416 |
kWh
|
$0.084 |
| Electricity Demand | $21,517 | 4,182 |
kW-mo/yr
|
$5.15 |
| Electricity Fees | $5,153 | - |
|
- |
| Natural Gas | $77,030 | 7,050 |
MMBtu
|
$10.93 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $17,044 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $8,259 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings |
|---|---|---|---|---|---|---|---|---|
| 01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $8,259 | $39,310 |
$6,035
71,657
kWh
|
$1,880
-
kW-mo/yr
|
$344 | - | |
| 02 | 2.7135: Install occupancy sensors | $3,058 | $2,513 |
$2,931
34,800
kWh
|
- | $127 | - | |
| 03 | 2.4231: Reduce the pressure of compressed air to the minimum required | $1,034 | $480 |
$589
6,995
kWh
|
$402
-
kW-mo/yr
|
$43 | - | |
| 04 | 2.4231: Reduce the pressure of compressed air to the minimum required | $806 | $480 |
$624
7,407
kWh
|
$148
-
kW-mo/yr
|
$34 | - | |
| 05 | 2.4239: Eliminate or reduce compressed air usage | $244 | $634 |
$123
1,459
kWh
|
$111
-
kW-mo/yr
|
$10 | - | |
| 06 | 2.7231: Use radiant heater for spot heating | $1,585 | $3,212 | - | - | - |
$1,585
-
MMBtu
|
|
| 07 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $1,356 | $2,344 |
$995
11,820
kWh
|
$318
-
kW-mo/yr
|
$43 | - | |
| 08 | 2.2136: Install / repair insulation on steam lines | $702 | $386 | - | - | - |
$702
-
MMBtu
|
|
| TOTAL RECOMMENDED | $17,044 | $49,359 |
$11,297
134,138
kWh
|
$2,859
-
kW-mo/yr
|
$601 |
$2,287
-
MMBtu
|
||
| TOTAL IMPLEMENTED | $8,259 | $39,310 |
$6,035
71,657
kWh
|
$1,880
-
kW-mo/yr
|
$344 | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs