Assessment Year | 2011 |
---|---|
Principal Product | Protective Apparel |
NAICS | 315990: Apparel Accessories and Other Apparel Manufacturing |
SIC | 2389: Apparel and Accessories, Not Elsewhere Classified |
Sales Range | $500 k to 1M |
# of Employees | 150 |
Plant Area |
114,920
ft2
|
Annual Production | 5,000
units
|
Production Hrs. Annual | 2,250
hrs
|
Location (State) | Alabama |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $88,405 | 1,025,684 |
kWh
|
$0.086 |
Electricity Demand | $28,077 | 4,150 |
kW-mo/yr
|
$6.77 |
Natural Gas | $37,206 | 3,802 |
MMBtu
|
$9.79 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $19,413 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $13,017 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.7221: Lower temperature during the winter season and vice-versa | $7,432 | $120 |
$2,991
34,710
kWh
|
$874
-
kW-mo/yr
|
$349 |
$3,218
-
MMBtu
|
|
02 | 2.4231: Reduce the pressure of compressed air to the minimum required | $4,859 | $480 |
$3,403
39,487
kWh
|
$1,228
-
kW-mo/yr
|
$228 | - | |
03 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $726 | $1,100 |
$605
7,023
kWh
|
$87
-
kW-mo/yr
|
$34 | - | |
04 | 2.7231: Use radiant heater for spot heating | $6,396 | $9,456 | - | - | - |
$6,396
-
MMBtu
|
|
TOTAL RECOMMENDED | $19,413 | $11,156 |
$6,999
81,220
kWh
|
$2,189
-
kW-mo/yr
|
$611 |
$9,614
-
MMBtu
|
||
TOTAL IMPLEMENTED | $13,017 | $1,700 |
$6,999
81,220
kWh
|
$2,189
-
kW-mo/yr
|
$611 |
$3,218
-
MMBtu
|
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs