Assessment Year | 2010 |
---|---|
Principal Product | office furniture |
NAICS | 337211: Wood Office Furniture Manufacturing |
SIC | 2521: Wood Office Furniture |
Sales Range | $10 M to 50M |
# of Employees | 174 |
Plant Area |
300,000
ft2
|
Annual Production | 300,000
pieces
|
Production Hrs. Annual | 4,680
hrs
|
Location (State) | Alabama |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $656,093 | 6,877,486 |
kWh
|
$0.095 |
Electricity Demand | $256,572 | 19,292 |
kW-mo/yr
|
$13.30 |
Natural Gas | $214,344 | 20,156 |
MMBtu
|
$10.63 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $229,287 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $8,282 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $65,946 | $165,576 |
$48,536
510,528
kWh
|
$17,410
-
kW-mo/yr
|
- | |
02 | 2.7135: Install occupancy sensors | $1,354 | $253 |
$1,354
14,240
kWh
|
- | - | |
03 | 2.7231: Use radiant heater for spot heating | $53,011 | $50,388 | - | - |
$53,011
-
MMBtu
|
|
04 | 2.7233: Use properly designed and sized hvac equipment | $29,964 | $19,014 |
$14,177
148,486
kWh
|
$15,787
-
kW-mo/yr
|
- | |
05 | 2.7221: Lower temperature during the winter season and vice-versa | $1,323 | - |
$1,323
13,913
kWh
|
- | - | |
06 | 2.4231: Reduce the pressure of compressed air to the minimum required | $35,672 | $740 |
$20,922
220,006
kWh
|
$14,750
-
kW-mo/yr
|
- | |
07 | 2.2437: Recover waste heat from equipment | $27,056 | $4,100 | - | - |
$27,056
-
MMBtu
|
|
08 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $5,605 | $5,500 |
$3,520
36,676
kWh
|
$2,085
-
kW-mo/yr
|
- | |
09 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $5,519 | $3,616 |
$4,003
42,111
kWh
|
$1,516
-
kW-mo/yr
|
- | |
10 | 2.4133: Use most efficient type of electric motors | $3,837 | $10,250 |
$2,785
29,298
kWh
|
$1,052
-
kW-mo/yr
|
- | |
TOTAL RECOMMENDED | $229,287 | $259,437 |
$96,620
1,015,258
kWh
|
$52,600
-
kW-mo/yr
|
$80,067
-
MMBtu
|
||
TOTAL IMPLEMENTED | $8,282 | $5,753 |
$6,197
64,829
kWh
|
$2,085
-
kW-mo/yr
|
- | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs