Assessment Year | 2024 |
---|---|
Principal Product | Boats |
NAICS | 336612: Boat Building |
SIC | 3732: Boat Building and Repairing |
Sales Range | $100 M to 500M |
# of Employees | 500 |
Plant Area |
312,588
ft2
|
Annual Production | 1,600
pieces
|
Production Hrs. Annual | 2,000
hrs
|
Location (State) | Tennessee |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | ||
---|---|---|---|---|---|
Electricity Usage | $523,008 | 7,353,360 |
kWh
|
$0.071 | |
Electricity Demand | $269,785 | 19,317 |
kW-mo/yr
|
$13.97 | |
Electricity Fees | $(-157,805.0) | - |
|
- | |
Natural Gas | $858,039 | 77,460 |
MMBtu
|
$11.08 | |
Waste Disposal Costs | |||||
Water Usage | $24,426 | 2,959 |
Tgal
|
$8.26 | |
Water Disposal | $10,460 | 1,208 |
Tgal
|
$8.66 | |
TOTAL YEARLY COSTS | $1,527,913 | ||||
RECOMMENDED SAVINGS* | $155,343 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | One-time Revenue or Avoided Cost Savings |
---|---|---|---|---|---|---|---|---|
01 | 4.212: Adopt in-house material generation | $30,976 | $12,000 |
$(-43.4)
(-610)
kWh
|
- | - | $31,019 | |
02 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $2,445 | $1,710 |
$2,445
34,379
kWh
|
- | - | - | |
03 | 2.2437: Recover waste heat from equipment | $17,320 | $15,000 | - | - |
$17,320
-
MMBtu
|
- | |
04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $18,949 | $23,783 |
$8,700
122,310
kWh
|
$10,249
-
kW-mo/yr
|
- | - | |
05 | 3.4116: Meter recycled water (to reduce sewer charges) | $6,052 | $7,500 | - | - | - | $6,052 | |
06 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $2,087 | $6,080 |
$2,087
29,340
kWh
|
- | - | - | |
07 | 2.9114: Use solar heat to make electricty | $57,337 | $238,118 |
$57,337
806,091
kWh
|
- | - | - | |
08 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $12,037 | $75,000 |
$10,961
154,100
kWh
|
$1,076
-
kW-mo/yr
|
- | - | |
09 | 2.4239: Eliminate or reduce compressed air usage | $8,140 | $26,000 |
$8,140
114,433
kWh
|
- | - | - | |
TOTAL RECOMMENDED | $155,343 | $405,191 |
$89,627
1,260,043
kWh
|
$11,325
-
kW-mo/yr
|
$17,320
-
MMBtu
|
$37,071 | ||
TOTAL IMPLEMENTED | - | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | One-time Revenue or Avoided Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs