| Assessment Year | 2021 |
|---|---|
| Principal Product | Pork Products |
| NAICS | 311611: Animal (except Poultry) Slaughtering |
| SIC | 2013: Sausages and Other Prepared Meat Products |
| Sales Range | $5 M to 10M |
| # of Employees | 130 |
| Plant Area |
69,000
ft2
|
| Annual Production | 200,000
units
|
| Production Hrs. Annual | 2,080
hrs
|
| Location (State) | Tennessee |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | ||
|---|---|---|---|---|---|
| Electricity Usage | $320,892 | 5,309,116 |
kWh
|
$0.060 | |
| Electricity Demand | $159,807 | 11,102 |
kW-mo/yr
|
$14.39 | |
| Natural Gas | $32,235 | 5,041 |
MMBtu
|
$6.39 | |
| Waste Disposal Costs | |||||
| Water Usage | $136,943 | 20,951 |
Tgal
|
$6.54 | |
| Water Disposal | $78,781 | 12,502 |
Tgal
|
$6.30 | |
| TOTAL YEARLY COSTS | $728,658 | ||||
| RECOMMENDED SAVINGS* | $39,375 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
| IMPLEMENTED SAVINGS* | $1,184 | ||||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Water Usage Savings |
|---|---|---|---|---|---|---|---|---|
| 01 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $12,890 | $3,640 |
$12,890
213,408
kWh
|
- | - | - | |
| 02 | 2.3212: Optimize plant power factor | $10,005 | $10,000 | - | - | $10,005 | - | |
| 03 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $6,928 | $300 |
$6,928
114,704
kWh
|
- | - | - | |
| 04 | 3.4159: Replace treated water with well / surface water | $4,069 | $16,500 | - | - | - |
$4,069
-
Tgal
|
|
| 05 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $2,791 | $1,660 |
$2,791
46,209
kWh
|
- | - | - | |
| 06 | 2.1311: Replace electrically-operated equipment with fossil fuel equipment | $1,508 | $3,500 |
$471
7,800
kWh
|
$1,037
-
kW-mo/yr
|
- | - | |
| 07 | 2.2511: Insulate bare equipment | $783 | $700 |
$783
12,965
kWh
|
- | - | - | |
| 08 | 2.7135: Install occupancy sensors | $401 | $553 |
$401
6,638
kWh
|
- | - | - | |
| TOTAL RECOMMENDED | $39,375 | $36,853 |
$24,264
401,724
kWh
|
$1,037
-
kW-mo/yr
|
$10,005 |
$4,069
-
Tgal
|
||
| TOTAL IMPLEMENTED | $1,184 | $1,253 |
$1,184
19,603
kWh
|
- | - | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Water Usage Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs