Assessment Year | 2019 |
---|---|
Principal Product | elevators |
NAICS | 333921: Elevator and Moving Stairway Manufacturing |
SIC | 3534: Elevators and Moving Stairways |
Sales Range | $50 M to 100M |
# of Employees | 496 |
Plant Area |
650,000
ft2
|
Annual Production | 11,652
units
|
Production Hrs. Annual | 5,824
hrs
|
Location (State) | Tennessee |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | ||
---|---|---|---|---|---|
Electricity Usage | $1,765,333 | 23,784,918 |
kWh
|
$0.074 | |
Electricity Demand | $684,243 | 57,192 |
kW-mo/yr
|
$11.96 | |
Natural Gas | $700,935 | 111,957 |
MMBtu
|
$6.26 | |
Waste Disposal Costs | |||||
Water Usage | $63,863 | 20,858 |
Tgal
|
$3.06 | |
Water Disposal | $98,328 | 20,858 |
Tgal
|
$4.71 | |
TOTAL YEARLY COSTS | $3,312,702 | ||||
RECOMMENDED SAVINGS* | $184,238 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
IMPLEMENTED SAVINGS* | $138,282 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Administrative Changes Savings | One-time Revenue or Avoided Cost Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $53,170 | $61,967 |
$42,582
573,884
kWh
|
$1,292
-
kW-mo/yr
|
- | $9,296 | - | |
02 | 2.4231: Reduce the pressure of compressed air to the minimum required | $50,161 | $360 |
$39,861
537,221
kWh
|
$10,300
-
kW-mo/yr
|
- | - | - | |
03 | 2.2515: Use optimum thickness insulation | $27,754 | $105,000 | - | - |
$27,754
-
MMBtu
|
- | - | |
04 | 2.6218: Turn off equipment when not in use | $18,588 | $10,000 |
$18,588
250,506
kWh
|
- | - | - | - | |
05 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $17,337 | $31,000 |
$12,076
162,752
kWh
|
$5,261
-
kW-mo/yr
|
- | - | - | |
06 | 2.7447: Install vinyl strip / high speed / air curtain doors | $7,306 | $18,000 |
$7,306
98,460
kWh
|
- | - | - | - | |
07 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $2,725 | $12,000 |
$2,725
36,731
kWh
|
- | - | - | - | |
08 | 2.7425: Clean or color roof to reduce solar load | $5,757 | $16,291 |
$5,757
77,577
kWh
|
- | - | - | - | |
09 | 4.812: Apply for investment incentives | $1,440 | - | - | - | - | - | $1,440 | |
TOTAL RECOMMENDED | $184,238 | $254,618 |
$128,895
1,737,131
kWh
|
$16,853
-
kW-mo/yr
|
$27,754
-
MMBtu
|
$9,296 | $1,440 | ||
TOTAL IMPLEMENTED | $138,282 | $183,618 |
$88,200
1,188,682
kWh
|
$11,592
-
kW-mo/yr
|
$27,754
-
MMBtu
|
$9,296 | $1,440 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Administrative Changes Savings | One-time Revenue or Avoided Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs