Assessment Year | 2014 |
---|---|
Principal Product | Mustard and Vinegar |
NAICS | 311941: Mayonnaise, Dressing, and Other Prepared Sauce Manufacturing |
SIC | 2035: Pickled Fruits and Vegetables, Vegetable Sauces and Seasonings, and Salad Dressings |
Sales Range | $10 M to 50M |
# of Employees | 79 |
Plant Area |
110,000
ft2
|
Annual Production | 225,120
Tgal
|
Production Hrs. Annual | 6,240
hrs
|
Location (State) | Tennessee |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $325,116 | 5,091,920 |
kWh
|
$0.064 |
Electricity Demand | $119,757 | 9,782 |
kW-mo/yr
|
$12.24 |
Electricity Fees | $6,978 | - |
|
- |
Natural Gas | $138,943 | 14,333 |
MMBtu
|
$9.69 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $15,397 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $11,367 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|
01 | 2.2135: Repair and eliminate steam leaks | $11,367 | $1,500 | - | - |
$11,367
-
MMBtu
|
|
02 | 2.2136: Install / repair insulation on steam lines | $764 | $505 | - | - |
$764
-
MMBtu
|
|
03 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $724 | $1,000 |
$724
11,307
kWh
|
- | - | |
04 | 2.7135: Install occupancy sensors | $148 | $240 |
$148
2,317
kWh
|
- | - | |
05 | 2.7135: Install occupancy sensors | $388 | $360 |
$388
6,059
kWh
|
- | - | |
06 | 2.7135: Install occupancy sensors | $724 | $720 |
$724
11,326
kWh
|
- | - | |
07 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,282 | $550 |
$981
15,320
kWh
|
$301
-
kW-mo/yr
|
- | |
TOTAL RECOMMENDED | $15,397 | $4,875 |
$2,965
46,329
kWh
|
$301
-
kW-mo/yr
|
$12,131
-
MMBtu
|
||
TOTAL IMPLEMENTED | $11,367 | $1,500 | - | - |
$11,367
-
MMBtu
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs