Assessment Year 2024
Principal Product Work, Dress, Casual, and Custom Boots
NAICS 316210: Footwear Manufacturing
SIC 3172: Personal Leather Goods, Except Women's Handbags and Purses
Sales Range $50
M
to 100
M
# of Employees 240
Plant Area 44,012
ft2
Annual Production 162,454
pieces
Production Hrs. Annual 2,300
hrs
Location (State) Texas

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $38,061 700,381
kWh
Electricity Demand $39,376 3,192
kW-mo/yr
Electricity Fees $4,027 -
LPG $49,714 2,700
MMBtu
TOTAL YEARLY COSTS $131,177
RECOMMENDED SAVINGS* $32,991 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* -

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Administrative Changes Savings
01 2.7142: Utilize higher efficiency lamps and/or ballasts $3,176 $6,207 $1,454
26,754
kWh
$1,722
-
kW-mo/yr
-
02 2.7232: Replace existing hvac unit with high efficiency model $12,921 $47,775 $7,723
142,123
kWh
$5,198
-
kW-mo/yr
-
03 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves $960 $1,000 $439
8,085
kWh
$520
-
kW-mo/yr
-
04 2.9114: Use solar heat to make electricty $11,908 $78,403 $8,669
159,519
kWh
$3,239
-
kW-mo/yr
-
05 2.8121: Apply for tax-free status for energy purchases $4,027 $2,500 - - $4,027
TOTAL RECOMMENDED $32,991 $135,885 $18,285
336,481
kWh
$10,679
-
kW-mo/yr
$4,027
TOTAL IMPLEMENTED - - - - -