| Assessment Year | 2000 |
|---|---|
| Principal Product | Steel nursing home, dormitory and detention furniture |
| NAICS |
n/a
|
| SIC | 2531: Public Building and Related Furniture |
| Sales Range | $10 M to 50M |
| # of Employees | 150 |
| Plant Area |
n/a
|
| Annual Production | 92,226
pieces
|
| Production Hrs. Annual | 4,335
hrs
|
| Location (State) | Texas |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $175,954 | 4,773,740 |
kWh
|
$0.037 |
| Electricity Demand | $68,746 | 10,245 |
kW-mo/yr
|
$6.71 |
| Natural Gas | $66,026 | 25,600 |
MMBtu
|
$2.58 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $23,900 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $19,503 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
|---|---|---|---|---|---|---|---|
| 01 | 2.7224: Reduce space conditioning during non-working hours | $8,751 | $5,000 |
$8,751
278,722
kWh
|
- | - | |
| 02 | 2.7124: Make a practice of turning off lights when not needed | $4,037 | - |
$2,615
72,685
kWh
|
$1,422
-
kW-mo/yr
|
- | |
| 03 | 2.2511: Insulate bare equipment | $2,307 | $1,326 | - | - |
$2,307
-
MMBtu
|
|
| 04 | 2.7124: Make a practice of turning off lights when not needed | $2,278 | - |
$2,278
72,685
kWh
|
- | - | |
| 05 | 2.4231: Reduce the pressure of compressed air to the minimum required | $1,733 | $20 |
$1,068
33,998
kWh
|
$665
-
kW-mo/yr
|
- | |
| 06 | 2.7135: Install occupancy sensors | $1,456 | - |
$1,456
46,307
kWh
|
- | - | |
| 07 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $1,423 | $280 |
$912
29,015
kWh
|
$511
-
kW-mo/yr
|
- | |
| 08 | 2.4314: Use synthetic lubricant | $595 | - |
$348
11,430
kWh
|
$247
-
kW-mo/yr
|
- | |
| 09 | 2.4133: Use most efficient type of electric motors | $613 | $6,187 |
$344
10,844
kWh
|
$269
-
kW-mo/yr
|
- | |
| 10 | 2.7124: Make a practice of turning off lights when not needed | $373 | - |
$373
10,258
kWh
|
- | - | |
| 11 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $334 | - |
$201
6,448
kWh
|
$133
-
kW-mo/yr
|
- | |
| TOTAL RECOMMENDED | $23,900 | $12,813 |
$18,346
572,392
kWh
|
$3,247
-
kW-mo/yr
|
$2,307
-
MMBtu
|
||
| TOTAL IMPLEMENTED | $19,503 | $6,606 |
$15,130
469,813
kWh
|
$2,066
-
kW-mo/yr
|
$2,307
-
MMBtu
|
||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs