Assessment Year 1999
Principal Product Laminated boards, laminate sheets, fiberglass sheets
NAICS
n/a
SIC 2541: Wood Office and Store Fixtures, Partitions, Shelving, and Lockers
Sales Range $10
M
to 50
M
# of Employees 75
Plant Area 175,000
ft2
Annual Production 39,000,000
lb
Production Hrs. Annual 6,240
hrs
Location (State) Tennessee

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $202,430 5,890,387
kWh
Electricity Demand $159,641 18,516
kW-mo/yr
Electricity Fees $10,364 -
Natural Gas $160,608 31,620
MMBtu
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $467,760 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $28,790

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Natural Gas Savings Solid Waste (non-haz) Savings Primary Product Savings
01 3.6123: Burn wood by-products for heat $194,600 $52,000 - - $74,600
-
MMBtu
$120,000
-
lb
-
02 3.5311: Recover and reuse waste material $120,000 $2,400 - - - $120,000
-
lb
-
03 3.5316: Contract a wood pallet recycling company $112,500 $32,000 - - - $112,500
-
lb
-
04 4.431: Train operators for maximum operating efficiency $25,000 $5,500 - - - - $25,000
05 2.7111: Reduce illumination to minimum necessary levels $9,160 $1,400 $4,920
153,869
kWh
$4,240
-
kW-mo/yr
- - -
06 2.7124: Make a practice of turning off lights when not needed $2,780 $2,630 $2,780
86,753
kWh
- - - -
07 2.4111: Utilize energy-efficient belts and other improved mechanisms $1,360 $1,330 $670
20,809
kWh
$690
-
kW-mo/yr
- - -
08 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves $1,010 $4,000 $665
20,809
kWh
$345
-
kW-mo/yr
- - -
09 2.2437: Recover waste heat from equipment $700 $810 - - $700
-
MMBtu
- -
10 2.4314: Use synthetic lubricant $650 - $310
9,672
kWh
$340
-
kW-mo/yr
- - -
TOTAL RECOMMENDED $467,760 $102,070 $9,345
291,912
kWh
$5,615
-
kW-mo/yr
$75,300
-
MMBtu
$352,500
-
lb
$25,000
TOTAL IMPLEMENTED $28,790 $12,130 $3,445
107,562
kWh
$345
-
kW-mo/yr
- - $25,000
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings Natural Gas Savings Solid Waste (non-haz) Savings Primary Product Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs