Assessment Year | 2003 |
---|---|
Principal Product | Relays and Control Valves |
NAICS | 335314: Relay and Industrial Control Manufacturing |
SIC | 3494: Valves and Pipe Fittings, Not Elsewhere Classified |
Sales Range | $50 M to 100M |
# of Employees | 250 |
Plant Area |
83,000
ft2
|
Annual Production | 4,400,000
pieces
|
Production Hrs. Annual | 3,863
hrs
|
Location (State) | Texas |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $424,887 | 8,759,614 |
kWh
|
$0.049 |
Electricity Demand | $94,577 | 21,977 |
kW-mo/yr
|
$4.30 |
Electricity Fees | $4,775 | - |
|
- |
Natural Gas | $14,151 | 1,975 |
MMBtu
|
$7.17 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $40,560 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $36,000 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|
01 | 2.4231: Reduce the pressure of compressed air to the minimum required | $31,140 | $17,080 |
$26,650
562,590
kWh
|
$4,490
-
kW-mo/yr
|
- | |
02 | 2.7111: Reduce illumination to minimum necessary levels | $2,330 | $240 |
$1,900
40,280
kWh
|
$430
-
kW-mo/yr
|
- | |
03 | 2.7228: Avoid introducing hot, humid, or dirty air into hvac system | $2,000 | $300 |
$2,000
42,180
kWh
|
- | - | |
04 | 2.2523: Reduce infiltration to refrigerated areas; isolate hot equipment from refrigerated areas | $1,870 | $435 |
$480
10,176
kWh
|
- |
$1,390
-
MMBtu
|
|
05 | 2.7135: Install occupancy sensors | $1,100 | $1,730 |
$1,100
23,550
kWh
|
- | - | |
06 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $690 | - |
$530
11,200
kWh
|
$160
-
kW-mo/yr
|
- | |
07 | 2.7121: Utilize daylight whenever possible in lieu of artificial light | $400 | - |
$400
8,550
kWh
|
- | - | |
08 | 2.7135: Install occupancy sensors | $350 | $170 |
$350
7,350
kWh
|
- | - | |
09 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $300 | $283 |
$270
5,641
kWh
|
$30
-
kW-mo/yr
|
- | |
10 | 2.7122: Disconnect ballasts | $140 | $270 |
$100
2,170
kWh
|
$40
-
kW-mo/yr
|
- | |
11 | 2.2511: Insulate bare equipment | $140 | $255 |
$140
3,000
kWh
|
- | - | |
12 | 2.6218: Turn off equipment when not in use | $100 | - |
$100
2,132
kWh
|
- | - | |
TOTAL RECOMMENDED | $40,560 | $20,763 |
$34,020
718,819
kWh
|
$5,150
-
kW-mo/yr
|
$1,390
-
MMBtu
|
||
TOTAL IMPLEMENTED | $36,000 | $18,098 |
$29,930
631,787
kWh
|
$4,680
-
kW-mo/yr
|
$1,390
-
MMBtu
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs