Assessment Year | 2025 |
---|---|
Principal Product | Notepads, Sewing Operation |
NAICS | 339999: All Other Miscellaneous Manufacturing |
SIC | 8331: Job Training and Vocational Rehabilitation Services |
Sales Range | $10 M to 50M |
# of Employees | 141 |
Plant Area |
75,000
ft2
|
Annual Production | 825,553
units
|
Production Hrs. Annual | 2,860
hrs
|
Location (State) | New York |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $57,034 | 730,426 |
kWh
|
$0.078 |
Electricity Demand | $51,659 | 2,508 |
kW-mo/yr
|
$20.60 |
Electricity Fees | $17,848 | - |
|
- |
Natural Gas | $16,768 | 2,821 |
MMBtu
|
$5.94 |
TOTAL YEARLY COSTS | $143,310 | |||
RECOMMENDED SAVINGS* | $47,252 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | One-time Revenue or Avoided Cost Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.4322: Use or replace with energy efficient substitutes | $1,783 | - |
$1,115
14,300
kWh
|
$1,030
-
kW-mo/yr
|
$(-362.5)
-
MMBtu
|
- | |
02 | 2.7224: Reduce space conditioning during non-working hours | $4,651 | - | - | - |
$4,651
-
MMBtu
|
- | |
03 | 2.3131: Reschedule plant operations or reduce load to avoid peaks | $2,576 | - | - |
$2,576
-
kW-mo/yr
|
- | - | |
04 | 2.4239: Eliminate or reduce compressed air usage | $144 | - |
$144
1,835
kWh
|
- | - | - | |
05 | 2.8121: Apply for tax-free status for energy purchases | $2,035 | $65 | - | - | - | $2,035 | |
06 | 2.2511: Insulate bare equipment | $813 | $751 | - | - |
$813
-
MMBtu
|
- | |
07 | 2.4322: Use or replace with energy efficient substitutes | $673 | $691 |
$355
4,555
kWh
|
$129
-
kW-mo/yr
|
- | $189 | |
08 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $4,746 | $5,006 |
$1,651
21,164
kWh
|
$1,829
-
kW-mo/yr
|
- | $1,266 | |
09 | 2.6211: Conserve energy by efficient use of vending machines | $167 | $359 |
$167
2,146
kWh
|
- | - | - | |
10 | 2.9114: Use solar heat to make electricty | $29,664 | $180,240 |
$29,664
380,312
kWh
|
- | - | - | |
TOTAL RECOMMENDED | $47,252 | $187,112 |
$33,097
424,312
kWh
|
$5,564
-
kW-mo/yr
|
$5,102
-
MMBtu
|
$3,489 | ||
TOTAL IMPLEMENTED | - | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | One-time Revenue or Avoided Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs