Assessment Year 2024
Principal Product Broad Band Communication Products
NAICS 334417: Electronic Connector Manufacturing
SIC 3663: Radio and Television Broadcasting and Communications Equipment
Sales Range $100
M
to 500
M
# of Employees 315
Plant Area 80,000
ft2
Annual Production 940,000
units
Production Hrs. Annual 6,240
hrs
Location (State) New York

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $444,636 5,909,053
kWh
Electricity Demand $154,058 12,101
kW-mo/yr
Electricity Fees $16,101 -
Natural Gas $42,764 5,843
MMBtu
Other Gas $1,220 1
MMBtu
TOTAL YEARLY COSTS $658,778
RECOMMENDED SAVINGS* $229,515 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* -

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Electricity Fees Savings Natural Gas Savings Personnel Changes Savings Administrative Changes Savings
01 3.1191: Change procedures / equipment / operating conditions $616 - - - - $616
-
MMBtu
- -
02 2.3132: Recharge batteries on during off-peak demand periods $2,970 - - $2,970
-
kW-mo/yr
- - - -
03 2.3131: Reschedule plant operations or reduce load to avoid peaks $7,702 - - $7,702
-
kW-mo/yr
- - - -
04 2.4239: Eliminate or reduce compressed air usage $1,953 - $1,953
26,045
kWh
- - - - -
05 2.8121: Apply for tax-free status for energy purchases $813 $105 - - $813 - - -
06 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves $1,067 $135 $1,067
14,222
kWh
- - - - -
07 2.7142: Utilize higher efficiency lamps and/or ballasts $9,403 $8,340 $5,653
75,378
kWh
$2,394
-
kW-mo/yr
- - - $1,356
08 2.7142: Utilize higher efficiency lamps and/or ballasts $444 $544 $226
3,013
kWh
$52
-
kW-mo/yr
- - $166 -
09 2.6211: Conserve energy by efficient use of vending machines $690 $1,542 $690
9,198
kWh
- - - - -
10 2.7234: Use heat pump for space conditioning $129,448 $632,250 $(-150,789.0)
(-2,010,528)
kWh
- - $280,237
-
MMBtu
- -
11 2.9114: Use solar heat to make electricty $74,409 $461,768 $74,409
992,124
kWh
- - - - -
TOTAL RECOMMENDED $229,515 $1,104,684 $(-66,790.5)
(-890,548)
kWh
$13,117
-
kW-mo/yr
$813 $280,853
-
MMBtu
$166 $1,356
TOTAL IMPLEMENTED - - - - - - - -
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings Electricity Fees Savings Natural Gas Savings Personnel Changes Savings Administrative Changes Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs