Assessment Year | 2024 |
---|---|
Principal Product | Custom made doors, some windows |
NAICS | 321911: Wood Window and Door Manufacturing |
SIC | 2431: Millwork |
Sales Range | $1 M to 5M |
# of Employees | 18 |
Plant Area |
33,000
ft2
|
Annual Production | 10,000
units
|
Production Hrs. Annual | 2,080
hrs
|
Location (State) | New York |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $43,824 | 581,420 |
kWh
|
$0.075 |
Electricity Demand | $40,016 | 3,163 |
kW-mo/yr
|
$12.65 |
Electricity Fees | $10,138 | - |
|
- |
TOTAL YEARLY COSTS | $93,979 | |||
RECOMMENDED SAVINGS* | $23,952 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | One-time Revenue or Avoided Cost Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.3131: Reschedule plant operations or reduce load to avoid peaks | $1,981 | - | - |
$1,981
-
kW-mo/yr
|
- | - | - | |
02 | 4.821: Pay bills on time to avoid late fees | $1,892 | - | - | - | $1,892 | - | - | |
03 | 2.4239: Eliminate or reduce compressed air usage | $984 | - |
$984
13,114
kWh
|
- | - | - | - | |
04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $2,574 | $129 |
$205
2,733
kWh
|
$47
-
kW-mo/yr
|
- | - | $2,322 | |
05 | 2.8121: Apply for tax-free status for energy purchases | $853 | $45 | - | - | - | - | $853 | |
06 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $1,796 | $218 |
$1,796
23,947
kWh
|
- | - | - | - | |
07 | 2.2437: Recover waste heat from equipment | $1,187 | $205 | - | - | - |
$1,187
-
MMBtu
|
- | |
08 | 2.8227: Adjust / maintain fork lift trucks for most efficient operation | $10,295 | $12,000 |
$(-2,625.0)
(-35,000)
kWh
|
- | - | - | $12,920 | |
09 | 2.4239: Eliminate or reduce compressed air usage | $370 | $433 |
$370
4,929
kWh
|
- | - | - | - | |
10 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $2,021 | $4,746 |
$1,246
16,609
kWh
|
$815
-
kW-mo/yr
|
- | - | $(-39.6) | |
TOTAL RECOMMENDED | $23,952 | $17,776 |
$1,975
26,331
kWh
|
$2,843
-
kW-mo/yr
|
$1,892 |
$1,187
-
MMBtu
|
$16,056 | ||
TOTAL IMPLEMENTED | - | - | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | One-time Revenue or Avoided Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs