| Assessment Year | 2023 |
|---|---|
| Principal Product | Toner, Printer and Copiers |
| NAICS | 333316: Photographic and Photocopying Equipment Manufacturing |
| SIC | 3861: Photographic Equipment and Supplies |
| Sales Range | $1 M to 5M |
| # of Employees | 177 |
| Plant Area |
1,200,000
ft2
|
| Annual Production | 1,203,257
units
|
| Production Hrs. Annual | 2,340
hrs
|
| Location (State) | New York |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $1,475,232 | 23,861,205 |
kWh
|
$0.062 |
| Electricity Demand | $538,529 | 48,968 |
kW-mo/yr
|
$11.00 |
| Natural Gas | $669,068 | 123,360 |
MMBtu
|
$5.42 |
| TOTAL YEARLY COSTS | $2,682,829 | |||
| RECOMMENDED SAVINGS* | $127,016 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | - | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | One-time Revenue or Avoided Cost Savings |
|---|---|---|---|---|---|---|---|---|
| 01 | 2.4239: Eliminate or reduce compressed air usage | $16,716 | - |
$16,716
278,598
kWh
|
- | - | - | |
| 02 | 2.7122: Disconnect ballasts | $568 | - |
$378
6,307
kWh
|
$190
-
kW-mo/yr
|
- | - | |
| 03 | 2.3132: Recharge batteries on during off-peak demand periods | $8,316 | - | - | - | - | $8,316 | |
| 04 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $14,574 | $1,108 |
$14,574
242,896
kWh
|
- | - | - | |
| 05 | 2.4322: Use or replace with energy efficient substitutes | $9,713 | $788 |
$5,738
95,625
kWh
|
$6,188
-
kW-mo/yr
|
$(-2,212.0)
-
MMBtu
|
- | |
| 06 | 2.4221: Install compressor air intakes in coolest locations | $7,990 | $1,122 |
$7,990
133,167
kWh
|
- | - | - | |
| 07 | 2.2135: Repair and eliminate steam leaks | $3,844 | $1,670 | - | - |
$3,844
-
MMBtu
|
- | |
| 08 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $633 | $352 |
$405
6,745
kWh
|
$101
-
kW-mo/yr
|
- | $127 | |
| 09 | 2.7135: Install occupancy sensors | $3,016 | $3,253 |
$3,016
50,263
kWh
|
- | - | - | |
| 10 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $60,779 | $108,879 |
$35,640
594,016
kWh
|
$16,906
-
kW-mo/yr
|
- | $8,233 | |
| 11 | 2.6211: Conserve energy by efficient use of vending machines | $867 | $1,863 |
$867
14,444
kWh
|
- | - | - | |
| TOTAL RECOMMENDED | $127,016 | $119,034 |
$85,323
1,422,060
kWh
|
$23,385
-
kW-mo/yr
|
$1,632
-
MMBtu
|
$16,676 | ||
| TOTAL IMPLEMENTED | - | - | - | - | - | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | One-time Revenue or Avoided Cost Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs