| Assessment Year | 2023 |
|---|---|
| Principal Product | Gas and Leak Detection Equipment |
| NAICS | 334513: Instruments and Related Products Manufacturing for Measuring, Displaying, and Controlling Industrial |
| SIC | 3823: Industrial Instruments for Measurement, Display, and Control of Process Variables; and Related Products |
| Sales Range | less than $500 k |
| # of Employees | 320 |
| Plant Area |
204,000
ft2
|
| Annual Production | 500
units
|
| Production Hrs. Annual | 3,060
hrs
|
| Location (State) | New York |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $461,966 | 6,136,728 |
kWh
|
$0.075 |
| Electricity Demand | $125,605 | 10,804 |
kW-mo/yr
|
$11.63 |
| Natural Gas | $13,308 | 7,376 |
MMBtu
|
$1.80 |
| TOTAL YEARLY COSTS | $600,880 | |||
| RECOMMENDED SAVINGS* | $31,244 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | - | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | One-time Revenue or Avoided Cost Savings |
|---|---|---|---|---|---|---|---|---|
| 01 | 2.7122: Disconnect ballasts | $1,626 | - |
$1,010
13,415
kWh
|
$616
-
kW-mo/yr
|
- | - | |
| 02 | 2.7314: Reduce ventilation air | $10,262 | $5,600 |
$5,720
75,969
kWh
|
- |
$4,542
-
MMBtu
|
- | |
| 03 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $2,866 | $1,925 |
$2,866
38,060
kWh
|
- | - | - | |
| 04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $16,490 | $11,867 |
$10,187
135,283
kWh
|
$6,170
-
kW-mo/yr
|
- | $133 | |
| TOTAL RECOMMENDED | $31,244 | $19,392 |
$19,783
262,727
kWh
|
$6,786
-
kW-mo/yr
|
$4,542
-
MMBtu
|
$133 | ||
| TOTAL IMPLEMENTED | - | - | - | - | - | - | ||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs