Assessment Year | 2004 |
---|---|
Principal Product | Paper containers |
NAICS | 322219: Other Paperboard Container Manufacturing |
SIC | 2656: Sanitary Food Containers, Except Folding |
Sales Range | $10 M to 50M |
# of Employees | 87 |
Plant Area |
85,400
ft2
|
Annual Production | 25,000
ton
|
Production Hrs. Annual | 6,240
hrs
|
Location (State) | Massachusetts |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $177,360 | 2,493,188 |
kWh
|
$0.071 |
Electricity Demand | $109,660 | 7,494 |
kW-mo/yr
|
$14.63 |
Electricity Fees | $2,000 | - |
|
- |
Natural Gas | $120,711 | 15,085 |
MMBtu
|
$8.00 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $61,586 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $38,303 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | By-product Production Savings |
---|---|---|---|---|---|---|---|---|
01 | 4.424: Improve space comfort conditioning | $17,360 | $17,910 |
$(-1,840.0)
(-28,400)
kWh
|
- | - | $19,200 | |
02 | 2.3212: Optimize plant power factor | $13,042 | $6,750 | - |
$13,042
-
kW-mo/yr
|
- | - | |
03 | 2.4239: Eliminate or reduce compressed air usage | $9,720 | $10,350 |
$9,720
147,500
kWh
|
- | - | - | |
04 | 2.2437: Recover waste heat from equipment | $4,840 | $2,131 | - | - |
$4,840
-
MMBtu
|
- | |
05 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $6,167 | $10,200 |
$3,453
52,400
kWh
|
$2,714
-
kW-mo/yr
|
- | - | |
06 | 2.5111: Convert from indirect to direct fired systems | $5,923 | $12,926 |
$932
14,200
kWh
|
$4,991
-
kW-mo/yr
|
- | - | |
07 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $4,534 | $529 |
$4,534
68,800
kWh
|
- | - | - | |
TOTAL RECOMMENDED | $61,586 | $60,796 |
$16,799
254,500
kWh
|
$20,747
-
kW-mo/yr
|
$4,840
-
MMBtu
|
$19,200 | ||
TOTAL IMPLEMENTED | $38,303 | $29,960 |
$17,707
268,700
kWh
|
$15,756
-
kW-mo/yr
|
$4,840
-
MMBtu
|
- | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | By-product Production Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs