| Assessment Year | 2023 |
|---|---|
| Principal Product | Mass Transit bus and commute bus manufacturing |
| NAICS | 336120: Heavy Duty Truck Manufacturing |
| SIC | 3711: Motor Vehicles and Passenger Car Bodies |
| Sales Range | $100 M to 500M |
| # of Employees | 394 |
| Plant Area |
161,250
ft2
|
| Annual Production | 535
units
|
| Production Hrs. Annual | 4,125
hrs
|
| Location (State) | New York |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $56,820 | 1,337,222 |
kWh
|
$0.042 |
| Electricity Demand | $39,468 | 4,578 |
kW-mo/yr
|
$8.62 |
| Electricity Fees | $2,135 | - |
|
- |
| Natural Gas | $90,374 | 25,106 |
MMBtu
|
$3.60 |
| TOTAL YEARLY COSTS | $188,797 | |||
| RECOMMENDED SAVINGS* | $101,388 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | - | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | One-time Revenue or Avoided Cost Savings |
|---|---|---|---|---|---|---|---|---|
| 01 | 2.7122: Disconnect ballasts | $14,621 | - |
$9,289
221,158
kWh
|
$5,332
-
kW-mo/yr
|
- | - | |
| 02 | 2.4239: Eliminate or reduce compressed air usage | $2,026 | - |
$2,026
48,429
kWh
|
- | - | - | |
| 03 | 2.8121: Apply for tax-free status for energy purchases | $4,522 | $26 | - | - | - | $4,522 | |
| 04 | 2.8121: Apply for tax-free status for energy purchases | $1,708 | $26 | - | - | - | $1,708 | |
| 05 | 2.4322: Use or replace with energy efficient substitutes | $877 | $32 |
$669
15,938
kWh
|
$453
-
kW-mo/yr
|
$(-244.7)
-
MMBtu
|
- | |
| 06 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $484 | $224 |
$320
7,621
kWh
|
$90
-
kW-mo/yr
|
- | $74 | |
| 07 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $3,990 | $1,787 |
$3,990
95,000
kWh
|
- | - | - | |
| 08 | 2.2511: Insulate bare equipment | $18,264 | $9,030 |
$(-732.1)
(-17,430)
kWh
|
$(-1,086.1)
-
kW-mo/yr
|
$20,082
-
MMBtu
|
- | |
| 09 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $14,474 | $24,111 |
$8,128
193,513
kWh
|
$4,666
-
kW-mo/yr
|
- | $1,680 | |
| 10 | 2.9114: Use solar heat to make electricty | $40,423 | $248,940 |
$40,423
856,250
kWh
|
- | - | - | |
| TOTAL RECOMMENDED | $101,388 | $284,176 |
$64,113
1,420,478
kWh
|
$9,454
-
kW-mo/yr
|
$19,837
-
MMBtu
|
$7,984 | ||
| TOTAL IMPLEMENTED | - | - | - | - | - | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | One-time Revenue or Avoided Cost Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs