Assessment Year 2022
Principal Product solenoids, valves, flame arrestors, sensors
NAICS 332911: Industrial Valve Manufacturing
SIC 3491: Industrial Valves
Sales Range $10
M
to 50
M
# of Employees 597
Plant Area 332,000
ft2
Annual Production 1,000,000
lb
Production Hrs. Annual 6,240
hrs
Location (State) New York

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $596,214 12,055,851
kWh
Electricity Demand $120,384 28,707
kW-mo/yr
Electricity Fees $53 -
Natural Gas $163,245 64,434
MMBtu
LPG $6,236 183
MMBtu
TOTAL YEARLY COSTS $886,133
RECOMMENDED SAVINGS* $36,376 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* -

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Natural Gas Savings LPG Savings One-time Revenue or Avoided Cost Savings
01 2.4239: Eliminate or reduce compressed air usage $7,482 - $7,482
152,689
kWh
- - - -
02 2.4322: Use or replace with energy efficient substitutes $108 $13 $82
1,680
kWh
$44
-
kW-mo/yr
$(-18.1)
-
MMBtu
- -
03 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves $1,804 $450 $1,804
36,822
kWh
- - - -
04 2.4221: Install compressor air intakes in coolest locations $7,215 $2,239 $7,215
147,252
kWh
- - - -
05 2.7142: Utilize higher efficiency lamps and/or ballasts $1,101 $350 $876
17,870
kWh
$205
-
kW-mo/yr
- - $20
06 2.1321: Replace fossil fuel equipment with electrical equipment $5,807 $3,000 $(-428.8)
(-8,750)
kWh
- - $6,236
-
MMBtu
-
07 2.2622: Replace existing chiller with high efficiency model $12,346 $12,588 $11,052
225,552
kWh
$1,294
-
kW-mo/yr
- - -
08 2.6211: Conserve energy by efficient use of vending machines $305 $664 $305
6,220
kWh
- - - -
09 2.2136: Install / repair insulation on steam lines $207 $487 - - $207
-
MMBtu
- -
TOTAL RECOMMENDED $36,376 $19,790 $28,388
579,335
kWh
$1,543
-
kW-mo/yr
$189
-
MMBtu
$6,236
-
MMBtu
$20
TOTAL IMPLEMENTED - - - - - - -
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings Natural Gas Savings LPG Savings One-time Revenue or Avoided Cost Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs