Assessment Year | 2022 |
---|---|
Principal Product | Milk Ingredients |
NAICS | 311511: Fluid Milk Manufacturing |
SIC | 2026: Fluid Milk |
Sales Range | $50 M to 100M |
# of Employees | 92 |
Plant Area |
116,000
ft2
|
Annual Production | 857,382,266
lb
|
Production Hrs. Annual | 8,760
hrs
|
Location (State) | New York |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | ||
---|---|---|---|---|---|
Electricity Usage | $1,202,710 | 21,921,643 |
kWh
|
$0.055 | |
Electricity Demand | $360,265 | 39,852 |
kW-mo/yr
|
$9.04 | |
Electricity Fees | $31,451 | - |
|
- | |
Natural Gas | $1,187,782 | 326,125 |
MMBtu
|
$3.64 | |
Waste Disposal Costs | |||||
Water Usage | $248,608 | 66,591 |
Tgal
|
$3.73 | |
TOTAL YEARLY COSTS | $3,030,815 | ||||
RECOMMENDED SAVINGS* | $116,486 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
IMPLEMENTED SAVINGS* | $2,741 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | Ancillary Material Cost Savings | One-time Revenue or Avoided Cost Savings |
---|---|---|---|---|---|---|---|---|---|---|
01 | 2.7224: Reduce space conditioning during non-working hours | $251 | - | - | - | - |
$251
-
MMBtu
|
- | - | |
02 | 2.4322: Use or replace with energy efficient substitutes | $1,425 | $41 |
$630
11,475
kWh
|
$973
-
kW-mo/yr
|
$(-178.2) | - | - | - | |
03 | 2.8121: Apply for tax-free status for energy purchases | $10,530 | $135 | - | - | $10,530 | - | - | - | |
04 | 2.8121: Apply for tax-free status for energy purchases | $14,616 | $135 | - | - | $14,616 | - | - | - | |
05 | 2.4239: Eliminate or reduce compressed air usage | $15,018 | - |
$15,018
273,076
kWh
|
- | - | - | - | - | |
06 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $2,741 | $291 |
$453
8,235
kWh
|
$102
-
kW-mo/yr
|
- | - | $1,822 | $364 | |
07 | 2.7135: Install occupancy sensors | $32,888 | $9,178 |
$32,888
597,962
kWh
|
- | - | - | - | - | |
08 | 2.4239: Eliminate or reduce compressed air usage | $3,090 | $1,343 |
$3,090
56,189
kWh
|
- | - | - | - | - | |
09 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $34,658 | $28,347 |
$27,797
506,328
kWh
|
$6,249
-
kW-mo/yr
|
- | - | - | $612 | |
10 | 2.7314: Reduce ventilation air | $1,232 | $1,265 |
$680
12,357
kWh
|
- | - |
$552
-
MMBtu
|
- | - | |
11 | 2.6211: Conserve energy by efficient use of vending machines | $36 | $162 |
$36
657
kWh
|
- | - | - | - | - | |
TOTAL RECOMMENDED | $116,486 | $40,897 |
$80,592
1,466,279
kWh
|
$7,324
-
kW-mo/yr
|
$24,969 |
$803
-
MMBtu
|
$1,822 | $976 | ||
TOTAL IMPLEMENTED | $2,741 | $291 |
$453
8,235
kWh
|
$102
-
kW-mo/yr
|
- | - | $1,822 | $364 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | Ancillary Material Cost Savings | One-time Revenue or Avoided Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs