Assessment Year | 2021 |
---|---|
Principal Product | Automotive Heat exchangers |
NAICS | 336390: Other Motor Vehicle Parts Manufacturing |
SIC | 3714: Motor Vehicle Parts and Accessories |
Sales Range | $10 M to 50M |
# of Employees | 120 |
Plant Area |
272,000
ft2
|
Annual Production | 15,000
units
|
Production Hrs. Annual | 2,610
hrs
|
Location (State) | New York |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $40,657 | 2,699,042 |
kWh
|
$0.015 |
Electricity Demand | $193,798 | 26,257 |
kW-mo/yr
|
$7.38 |
Electricity Fees | $48,368 | - |
|
- |
Natural Gas | $116,630 | 42,627 |
MMBtu
|
$2.74 |
Other Energy | $3,902 | 4,558,597 |
MMBtu
|
$0.001 |
TOTAL YEARLY COSTS | $403,355 | |||
RECOMMENDED SAVINGS* | $58,035 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $5,108 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings | One-time Revenue or Avoided Cost Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 4.821: Pay bills on time to avoid late fees | $1,720 | - | - | - | - | - | $1,720 | |
02 | 2.8121: Apply for tax-free status for energy purchases | $23,973 | $120 | - | - | - | - | $23,973 | |
03 | 2.8121: Apply for tax-free status for energy purchases | $7,147 | $120 | - | - | - | - | $7,147 | |
04 | 2.7314: Reduce ventilation air | $4,625 | $882 |
$709
47,251
kWh
|
- |
$3,916
-
MMBtu
|
- | - | |
05 | 2.2136: Install / repair insulation on steam lines | $191 | $203 | - | - |
$191
-
MMBtu
|
- | - | |
06 | 3.1161: Eliminate/reduce an operation | $2,822 | $3,300 |
$(-16.5)
(-1,100)
kWh
|
$(-749.2)
-
kW-mo/yr
|
- | - | $3,588 | |
07 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $6,661 | $7,939 |
$1,621
108,068
kWh
|
$4,785
-
kW-mo/yr
|
- | - | $255 | |
08 | 2.7241: Install outside air damper / economizer on hvac unit | $10,521 | $22,840 | - | - |
$10,521
-
MMBtu
|
- | - | |
09 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $375 | $1,259 |
$63
4,205
kWh
|
$43
-
kW-mo/yr
|
- | $174 | $95 | |
TOTAL RECOMMENDED | $58,035 | $36,663 |
$2,377
158,424
kWh
|
$4,079
-
kW-mo/yr
|
$14,628
-
MMBtu
|
$174 | $36,778 | ||
TOTAL IMPLEMENTED | $5,108 | $4,762 |
$47
3,105
kWh
|
$(-706.7)
-
kW-mo/yr
|
$191
-
MMBtu
|
$174 | $5,403 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings | One-time Revenue or Avoided Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs