Assessment Year | 2020 |
---|---|
Principal Product | Bread |
NAICS | 311812: Commercial Bakeries |
SIC | 2051: Bread and Other Bakery Products, Except Cookies and Crackers |
Sales Range | $10 M to 50M |
# of Employees | 120 |
Plant Area |
73,524
ft2
|
Annual Production | 30,000,000
units
|
Production Hrs. Annual | 8,736
hrs
|
Location (State) | New York |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $272,611 | 3,983,994 |
kWh
|
$0.068 |
Electricity Demand | $95,489 | 15,623 |
kW-mo/yr
|
$6.11 |
Electricity Fees | $123 | - |
|
- |
Natural Gas | $179,567 | 44,119 |
MMBtu
|
$4.07 |
TOTAL YEARLY COSTS | $547,790 | |||
RECOMMENDED SAVINGS* | $28,744 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $10,087 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings | One-time Revenue or Avoided Cost Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.7224: Reduce space conditioning during non-working hours | $285 | - | - | - |
$285
-
MMBtu
|
- | - | |
02 | 2.4231: Reduce the pressure of compressed air to the minimum required | $5,803 | - |
$5,803
89,210
kWh
|
- | - | - | - | |
03 | 3.1161: Eliminate/reduce an operation | $11,303 | $3,012 |
$(-276.0)
(-4,061)
kWh
|
$(-620.0)
-
kW-mo/yr
|
- | - | $12,199 | |
04 | 2.4322: Use or replace with energy efficient substitutes | $327 | $294 |
$179
2,628
kWh
|
$22
-
kW-mo/yr
|
- | $65 | $61 | |
05 | 2.7135: Install occupancy sensors | $682 | $785 |
$682
10,029
kWh
|
- | - | - | - | |
06 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $10,087 | $14,773 |
$7,967
117,168
kWh
|
$1,342
-
kW-mo/yr
|
- | $1,556 | $(-778.0) | |
07 | 2.7135: Install occupancy sensors | $257 | $508 |
$257
3,778
kWh
|
- | - | - | - | |
TOTAL RECOMMENDED | $28,744 | $19,372 |
$14,612
218,752
kWh
|
$744
-
kW-mo/yr
|
$285
-
MMBtu
|
$1,621 | $11,482 | ||
TOTAL IMPLEMENTED | $10,087 | $14,773 |
$7,967
117,168
kWh
|
$1,342
-
kW-mo/yr
|
- | $1,556 | $(-778.0) | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings | One-time Revenue or Avoided Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs