| Assessment Year | 2017 |
|---|---|
| Principal Product | Thermal Fluid Heaters |
| NAICS | 333414: Heating Equipment (except Warm Air Furnaces) Manufacturing |
| SIC | 3433: Heating Equipment, Except Electric and Warm Air Furnaces |
| Sales Range | $10 M to 50M |
| # of Employees | 225 |
| Plant Area |
140,000
ft2
|
| Annual Production | 450
units
|
| Production Hrs. Annual | 4,030
hrs
|
| Location (State) | New York |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $78,190 | 2,029,453 |
kWh
|
$0.039 |
| Electricity Demand | $75,124 | 5,782 |
kW-mo/yr
|
$12.99 |
| Electricity Fees | $13,023 | - |
|
- |
| Natural Gas | $86,584 | 22,031 |
MMBtu
|
$3.93 |
| TOTAL YEARLY COSTS | $252,921 | |||
| RECOMMENDED SAVINGS* | $31,896 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $31,896 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Personnel Changes Savings | One-time Revenue or Avoided Cost Savings |
|---|---|---|---|---|---|---|---|---|
| 01 | 2.8121: Apply for tax-free status for energy purchases | $7,318 | - | - | - | - | $7,318 | |
| 02 | 2.8121: Apply for tax-free status for energy purchases | $3,262 | - | - | - | - | $3,262 | |
| 03 | 2.7135: Install occupancy sensors | $2,546 | $588 |
$2,546
65,286
kWh
|
- | - | - | |
| 04 | 3.1161: Eliminate/reduce an operation | $4,758 | $1,724 |
$(-91.0)
(-2,340)
kWh
|
$(-468.0)
-
kW-mo/yr
|
$1,612 | $3,705 | |
| 05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $730 | $685 |
$164
4,205
kWh
|
$75
-
kW-mo/yr
|
$357 | $134 | |
| 06 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $12,427 | $18,304 |
$6,381
163,618
kWh
|
$6,329
-
kW-mo/yr
|
$310 | $(-593.0) | |
| 07 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $631 | $1,080 |
$359
9,198
kWh
|
$327
-
kW-mo/yr
|
$6 | $(-61.0) | |
| 08 | 2.6211: Conserve energy by efficient use of vending machines | $224 | $903 |
$224
5,733
kWh
|
- | - | - | |
| TOTAL RECOMMENDED | $31,896 | $23,284 |
$9,583
245,700
kWh
|
$6,263
-
kW-mo/yr
|
$2,285 | $13,765 | ||
| TOTAL IMPLEMENTED | $31,896 | $23,284 |
$9,583
245,700
kWh
|
$6,263
-
kW-mo/yr
|
$2,285 | $13,765 | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Personnel Changes Savings | One-time Revenue or Avoided Cost Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs