| Assessment Year | 2016 |
|---|---|
| Principal Product | Refractory Systems |
| NAICS | 327120: Clay Building Material and Refractories Manufacturing |
| SIC | 3297: Nonclay Refractories |
| Sales Range | $10 M to 50M |
| # of Employees | 100 |
| Plant Area |
180,000
ft2
|
| Annual Production | 3,300,000
lb
|
| Production Hrs. Annual | 4,368
hrs
|
| Location (State) | New York |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $194,077 | 2,993,434 |
kWh
|
$0.065 |
| Electricity Demand | $60,018 | 7,139 |
kW-mo/yr
|
$8.41 |
| Electricity Fees | $7,445 | - |
|
- |
| Natural Gas | $117,557 | 25,233 |
MMBtu
|
$4.66 |
| TOTAL YEARLY COSTS | $379,097 | |||
| RECOMMENDED SAVINGS* | $15,060 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $4,061 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings | One-time Revenue or Avoided Cost Savings |
|---|---|---|---|---|---|---|---|---|---|
| 01 | 2.7122: Disconnect ballasts | $270 | - |
$199
3,058
kWh
|
$71
-
kW-mo/yr
|
- | - | - | |
| 02 | 2.4231: Reduce the pressure of compressed air to the minimum required | $2,312 | - |
$3,454
53,145
kWh
|
- | - | $(-1,142.0) | - | |
| 03 | 2.2123: Insulate feedwater tank | $162 | $56 | - | - |
$162
-
MMBtu
|
- | - | |
| 04 | 3.1161: Eliminate/reduce an operation | $10,608 | $4,074 |
$(-183.0)
(-2,820)
kWh
|
$(-569.0)
-
kW-mo/yr
|
- | $4,550 | $6,810 | |
| 05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $391 | $388 |
$97
1,490
kWh
|
$17
-
kW-mo/yr
|
- | $200 | $77 | |
| 06 | 2.6211: Conserve energy by efficient use of vending machines | $428 | $991 |
$428
6,581
kWh
|
- | - | - | - | |
| 07 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $132 | $393 |
$54
830
kWh
|
$19
-
kW-mo/yr
|
- | $55 | $4 | |
| 08 | 2.7135: Install occupancy sensors | $757 | $3,080 |
$757
11,648
kWh
|
- | - | - | - | |
| TOTAL RECOMMENDED | $15,060 | $8,982 |
$4,806
73,932
kWh
|
$(-462.0)
-
kW-mo/yr
|
$162
-
MMBtu
|
$3,663 | $6,891 | ||
| TOTAL IMPLEMENTED | $4,061 | $4,520 |
$4,892
75,262
kWh
|
$90
-
kW-mo/yr
|
$162
-
MMBtu
|
$(-1,087.0) | $4 | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings | One-time Revenue or Avoided Cost Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs