| Assessment Year | 2016 |
|---|---|
| Principal Product | Grease and Lubricating Oils |
| NAICS | 324191: Petroleum Lubricating Oil and Grease Manufacturing |
| SIC | 2992: Lubricating Oils and Greases |
| Sales Range | $10 M to 50M |
| # of Employees | 63 |
| Plant Area |
115,000
ft2
|
| Annual Production | 25,000,000
lb
|
| Production Hrs. Annual | 4,420
hrs
|
| Location (State) | New York |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | ||
|---|---|---|---|---|---|
| Electricity Usage | $59,750 | 1,211,257 |
kWh
|
$0.049 | |
| Electricity Demand | $87,743 | 7,850 |
kW-mo/yr
|
$11.18 | |
| Electricity Fees | $4,904 | - |
|
- | |
| Natural Gas | $62,144 | 10,777 |
MMBtu
|
$5.77 | |
| Waste Disposal Costs | |||||
| Water Usage | $24,600 | 6,483 |
Tgal
|
$3.79 | |
| TOTAL YEARLY COSTS | $239,141 | ||||
| RECOMMENDED SAVINGS* | $31,122 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
| IMPLEMENTED SAVINGS* | - | ||||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings | One-time Revenue or Avoided Cost Savings |
|---|---|---|---|---|---|---|---|---|---|
| 01 | 2.4314: Use synthetic lubricant | $6,457 | - |
$1,857
37,903
kWh
|
$4,600
-
kW-mo/yr
|
- | - | - | |
| 02 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $3,860 | - |
$1,110
22,653
kWh
|
$2,750
-
kW-mo/yr
|
- | - | - | |
| 03 | 2.4322: Use or replace with energy efficient substitutes | $1,141 | - |
$992
20,250
kWh
|
$2,012
-
kW-mo/yr
|
$(-1,863.0)
-
MMBtu
|
- | - | |
| 04 | 2.4231: Reduce the pressure of compressed air to the minimum required | $234 | - |
$234
4,784
kWh
|
- | - | - | - | |
| 05 | 2.2414: Use waste heat from hot flue gases to preheat | $19,089 | $33,000 | - | - |
$19,089
-
MMBtu
|
- | - | |
| 06 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $277 | $704 |
$137
2,803
kWh
|
$42
-
kW-mo/yr
|
- | $77 | $21 | |
| 07 | 2.6211: Conserve energy by efficient use of vending machines | $64 | $210 |
$64
1,314
kWh
|
- | - | - | - | |
| TOTAL RECOMMENDED | $31,122 | $33,914 |
$4,394
89,707
kWh
|
$9,404
-
kW-mo/yr
|
$17,226
-
MMBtu
|
$77 | $21 | ||
| TOTAL IMPLEMENTED | - | - | - | - | - | - | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings | One-time Revenue or Avoided Cost Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs