| Assessment Year | 2013 |
|---|---|
| Principal Product | Electronics |
| NAICS | 334412: Bare Printed Circuit Board Manufacturing |
| SIC | 3672: Printed Circuit Boards |
| Sales Range | $10 M to 50M |
| # of Employees | 150 |
| Plant Area |
30,000
ft2
|
| Annual Production | 3,537,660
pieces
|
| Production Hrs. Annual | 2,125
hrs
|
| Location (State) | New York |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $76,204 | 1,203,940 |
kWh
|
$0.063 |
| Electricity Demand | $39,816 | 4,871 |
kW-mo/yr
|
$8.17 |
| Electricity Fees | $3,988 | - |
|
- |
| Natural Gas | $21,009 | 1,937 |
MMBtu
|
$10.85 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $27,929 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $26,823 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Personnel Changes Savings | One-time Revenue or Avoided Cost Savings |
|---|---|---|---|---|---|---|---|---|
| 01 | 2.8114: Change rate schedules or other changes in utility service | $11,585 | - | - | - | - | $11,585 | |
| 02 | 2.8114: Change rate schedules or other changes in utility service | $8,541 | - | - | - | - | $8,541 | |
| 03 | 2.8121: Apply for tax-free status for energy purchases | $1,961 | - | - | - | - | $1,961 | |
| 04 | 2.4322: Use or replace with energy efficient substitutes | $1,426 | - |
$348
5,500
kWh
|
$1,078
-
kW-mo/yr
|
- | - | |
| 05 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $295 | - |
$99
1,561
kWh
|
$196
-
kW-mo/yr
|
- | - | |
| 06 | 2.7111: Reduce illumination to minimum necessary levels | $504 | $102 |
$292
4,611
kWh
|
$212
-
kW-mo/yr
|
- | - | |
| 07 | 2.7111: Reduce illumination to minimum necessary levels | $405 | $85 |
$233
3,677
kWh
|
$172
-
kW-mo/yr
|
- | - | |
| 08 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $1,799 | $740 |
$1,799
28,419
kWh
|
- | - | - | |
| 09 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $355 | $463 |
$139
2,190
kWh
|
$25
-
kW-mo/yr
|
$112 | $79 | |
| 10 | 2.4221: Install compressor air intakes in coolest locations | $430 | $1,448 |
$430
6,788
kWh
|
- | - | - | |
| 11 | 2.6211: Conserve energy by efficient use of vending machines | $357 | $376 |
$357
5,643
kWh
|
- | - | - | |
| 12 | 2.7135: Install occupancy sensors | $271 | $970 |
$271
4,282
kWh
|
- | - | - | |
| TOTAL RECOMMENDED | $27,929 | $4,184 |
$3,968
62,671
kWh
|
$1,683
-
kW-mo/yr
|
$112 | $22,166 | ||
| TOTAL IMPLEMENTED | $26,823 | $1,681 |
$3,034
47,924
kWh
|
$1,511
-
kW-mo/yr
|
$112 | $22,166 | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Personnel Changes Savings | One-time Revenue or Avoided Cost Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs