Assessment Year | 2012 |
---|---|
Principal Product | Sealing Products |
NAICS | 339991: Gasket, Packing, and Sealing Device Manufacturing |
SIC | 3053: Gaskets, Packing, and Sealing Devices |
Sales Range | $10 M to 50M |
# of Employees | 150 |
Plant Area |
350,000
ft2
|
Annual Production | 215,000
thousand feet
|
Production Hrs. Annual | 6,240
hrs
|
Location (State) | New York |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $437,218 | 8,129,315 |
kWh
|
$0.054 |
Electricity Demand | $148,093 | 17,513 |
kW-mo/yr
|
$8.46 |
Electricity Fees | $14,034 | - |
|
- |
Natural Gas | $186,260 | 28,769 |
MMBtu
|
$6.47 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $94,607 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $29,328 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | One-time Revenue or Avoided Cost Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.2136: Install / repair insulation on steam lines | $27,155 | $157 | - | - | - |
$27,155
-
MMBtu
|
- | |
02 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $2,173 | $328 |
$2,173
40,248
kWh
|
- | - | - | - | |
03 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $7,167 | $3,286 |
$7,167
132,720
kWh
|
- | - | - | - | |
04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $710 | $570 |
$156
2,891
kWh
|
$34
-
kW-mo/yr
|
- | - | $520 | |
05 | 2.7314: Reduce ventilation air | $3,824 | $4,193 |
$215
3,978
kWh
|
$173
-
kW-mo/yr
|
- |
$3,436
-
MMBtu
|
- | |
06 | 2.3212: Optimize plant power factor | $4,286 | $10,841 | - | - | $4,286 | - | - | |
07 | 2.6211: Conserve energy by efficient use of vending machines | $244 | $711 |
$244
4,525
kWh
|
- | - | - | - | |
08 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $179 | $760 |
$94
1,747
kWh
|
$85
-
kW-mo/yr
|
- | - | - | |
09 | 2.4321: Upgrade obsolete equipment | $145 | $703 |
$111
2,059
kWh
|
$34
-
kW-mo/yr
|
- | - | - | |
10 | 2.1311: Replace electrically-operated equipment with fossil fuel equipment | $48,724 | $900,000 |
$54,588
1,010,880
kWh
|
$16,452
-
kW-mo/yr
|
- |
$(-22,316.0)
-
MMBtu
|
- | |
TOTAL RECOMMENDED | $94,607 | $921,549 |
$64,748
1,199,048
kWh
|
$16,778
-
kW-mo/yr
|
$4,286 |
$8,275
-
MMBtu
|
$520 | ||
TOTAL IMPLEMENTED | $29,328 | $485 |
$2,173
40,248
kWh
|
- | - |
$27,155
-
MMBtu
|
- | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | One-time Revenue or Avoided Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs