Assessment Year | 2010 |
---|---|
Principal Product | Aluminum Foundry |
NAICS | 331524: Aluminum Foundries (except Die-Casting) |
SIC | 3365: Aluminum Foundries |
Sales Range | $10 M to 50M |
# of Employees | 51 |
Plant Area |
250,000
ft2
|
Annual Production | 106,000
units
|
Production Hrs. Annual | 4,250
hrs
|
Location (State) | New York |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $221,852 | 4,530,777 |
kWh
|
$0.049 |
Electricity Demand | $123,981 | 12,804 |
kW-mo/yr
|
$9.68 |
Electricity Fees | $21,427 | - |
|
- |
Natural Gas | $491,460 | 61,426 |
MMBtu
|
$8.00 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $90,464 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | One-time Revenue or Avoided Cost Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 4.821: Pay bills on time to avoid late fees | $21,457 | - | - | - | - | - | $21,457 | |
02 | 2.4231: Reduce the pressure of compressed air to the minimum required | $3,096 | - |
$3,096
51,600
kWh
|
- | - | - | - | |
03 | 2.2437: Recover waste heat from equipment | $9,218 | $1,248 | - | - | - |
$9,218
-
MMBtu
|
- | |
04 | 2.7135: Install occupancy sensors | $431 | $86 |
$228
3,804
kWh
|
$203
-
kW-mo/yr
|
- | - | - | |
05 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $792 | $266 |
$792
13,200
kWh
|
- | - | - | - | |
06 | 2.6211: Conserve energy by efficient use of vending machines | $125 | $274 |
$125
2,079
kWh
|
- | - | - | - | |
07 | 3.1191: Change procedures / equipment / operating conditions | $35,873 | $81,798 |
$(-1,919.0)
(-70,125)
kWh
|
$(-4,208.0)
-
kW-mo/yr
|
- | - | $42,000 | |
08 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $15,123 | $45,613 |
$10,385
173,063
kWh
|
$4,738
-
kW-mo/yr
|
- | - | - | |
09 | 2.3212: Optimize plant power factor | $4,349 | $17,933 | - | - | $4,349 | - | - | |
TOTAL RECOMMENDED | $90,464 | $147,218 |
$12,707
173,621
kWh
|
$733
-
kW-mo/yr
|
$4,349 |
$9,218
-
MMBtu
|
$63,457 | ||
TOTAL IMPLEMENTED | - | - | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | One-time Revenue or Avoided Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs