Assessment Year | 2007 |
---|---|
Principal Product | Heat Exchangers |
NAICS | 332410: Power Boiler and Heat Exchanger Manufacturing |
SIC | 3443: Fabricated Plate Work (Boiler Shops) |
Sales Range | $10 M to 50M |
# of Employees | 178 |
Plant Area |
110,930
ft2
|
Annual Production | 10,000,000
lb
|
Production Hrs. Annual | 6,240
hrs
|
Location (State) | New York |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $243,264 | 3,213,502 |
kWh
|
$0.076 |
Electricity Demand | $111,116 | 7,496 |
kW-mo/yr
|
$14.82 |
Electricity Fees | $5,954 | - |
|
- |
Natural Gas | $139,206 | 12,358 |
MMBtu
|
$11.26 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $71,105 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $21,806 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | Personnel Changes Savings | One-time Revenue or Avoided Cost Savings |
---|---|---|---|---|---|---|---|---|---|---|
01 | 2.8114: Change rate schedules or other changes in utility service | $9,744 | - | - | - | - | - | - | $9,744 | |
02 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $4,004 | - |
$2,907
38,252
kWh
|
$1,097
-
kW-mo/yr
|
- | - | - | - | |
03 | 4.821: Pay bills on time to avoid late fees | $765 | - | - | - | - | - | - | $765 | |
04 | 2.4314: Use synthetic lubricant | $336 | - |
$247
3,244
kWh
|
$89
-
kW-mo/yr
|
- | - | - | - | |
05 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $7,293 | $1,300 |
$5,307
69,826
kWh
|
$1,986
-
kW-mo/yr
|
- | - | - | - | |
06 | 2.7491: Insulate glazing, walls, ceilings, and roofs | $8,489 | $4,993 | - | - | - |
$8,489
-
MMBtu
|
- | - | |
07 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $331 | $237 |
$107
1,402
kWh
|
$30
-
kW-mo/yr
|
- | - | $141 | $53 | |
08 | 2.7496: Install partitions to reduce size of conditioned space | $14,202 | $19,571 | - | - | - |
$14,202
-
MMBtu
|
- | - | |
09 | 2.7243: Improve air circulation with destratification fans / other methods | $4,084 | $5,590 |
$(-402.0)
(-5,292)
kWh
|
$(-104.0)
-
kW-mo/yr
|
- |
$4,590
-
MMBtu
|
- | - | |
10 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $21,025 | $32,224 |
$15,290
201,177
kWh
|
$5,735
-
kW-mo/yr
|
- | - | - | - | |
11 | 2.6211: Conserve energy by efficient use of vending machines | $269 | $727 |
$269
3,533
kWh
|
- | - | - | - | - | |
12 | 2.3212: Optimize plant power factor | $563 | $3,344 | - | - | $563 | - | - | - | |
TOTAL RECOMMENDED | $71,105 | $67,986 |
$23,725
312,142
kWh
|
$8,833
-
kW-mo/yr
|
$563 |
$27,281
-
MMBtu
|
$141 | $10,562 | ||
TOTAL IMPLEMENTED | $21,806 | $1,300 |
$8,214
108,078
kWh
|
$3,083
-
kW-mo/yr
|
- | - | - | $10,509 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | Personnel Changes Savings | One-time Revenue or Avoided Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs