Assessment Year | 2005 |
---|---|
Principal Product | High Temperature Textiles |
NAICS | 313210: Broadwoven Fabric Mills |
SIC | 2221: Broadwoven Fabric Mills, Manmade Fiber and Silk |
Sales Range | $10 M to 50M |
# of Employees | 50 |
Plant Area |
96,200
ft2
|
Annual Production | 900,000
pieces
|
Production Hrs. Annual | 4,238
hrs
|
Location (State) | New York |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $146,914 | 1,594,506 |
kWh
|
$0.092 |
Electricity Demand | $66,050 | 6,332 |
kW-mo/yr
|
$10.43 |
Electricity Fees | $(-44,959.0) | - |
|
- |
Natural Gas | $78,410 | 8,622 |
MMBtu
|
$9.09 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $40,706 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $32,928 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|
01 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $2,587 | - |
$1,961
21,317
kWh
|
$626
-
kW-mo/yr
|
- | |
02 | 2.4231: Reduce the pressure of compressed air to the minimum required | $2,063 | - |
$1,416
15,390
kWh
|
$647
-
kW-mo/yr
|
- | |
03 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $328 | $143 |
$224
2,430
kWh
|
$104
-
kW-mo/yr
|
- | |
04 | 2.4314: Use synthetic lubricant | $1,943 | $1,000 |
$1,474
16,020
kWh
|
$469
-
kW-mo/yr
|
- | |
05 | 2.2442: Preheat combustion air with waste heat | $28,070 | $35,100 | - | - |
$28,070
-
MMBtu
|
|
06 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $5,715 | $11,225 |
$4,328
47,042
kWh
|
$1,387
-
kW-mo/yr
|
- | |
TOTAL RECOMMENDED | $40,706 | $47,468 |
$9,403
102,199
kWh
|
$3,233
-
kW-mo/yr
|
$28,070
-
MMBtu
|
||
TOTAL IMPLEMENTED | $32,928 | $36,243 |
$3,659
39,767
kWh
|
$1,199
-
kW-mo/yr
|
$28,070
-
MMBtu
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs