Assessment Year 2004
Principal Product Cable Connectors
NAICS 334220: Radio and Television Broadcasting and Wireless Communications Equipment Manufacturing
SIC 3451: Screw Machine Products
Sales Range $5
M
to 10
M
# of Employees 490
Plant Area 106,000
ft2
Annual Production 0
units
Production Hrs. Annual 6,240
hrs
Location (State) New York

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $499,528 6,598,400
kWh
Electricity Demand $190,650 13,476
kW-mo/yr
Electricity Fees $15,152 -
Natural Gas $68,915 889
MMBtu
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $65,327 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $44,118

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Electricity Fees Savings One-time Revenue or Avoided Cost Savings
01 2.8114: Change rate schedules or other changes in utility service $26,400 - - - - $26,400
02 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves $11,746 $527 $8,834
116,128
kWh
$2,912
-
kW-mo/yr
- -
03 2.7135: Install occupancy sensors $580 $214 $417
5,491
kWh
$163
-
kW-mo/yr
- -
04 2.7142: Utilize higher efficiency lamps and/or ballasts $21,209 $20,138 $15,620
205,527
kWh
$5,589
-
kW-mo/yr
- -
05 2.3212: Optimize plant power factor $5,392 $15,432 - - $5,392 -
TOTAL RECOMMENDED $65,327 $36,311 $24,871
327,146
kWh
$8,664
-
kW-mo/yr
$5,392 $26,400
TOTAL IMPLEMENTED $44,118 $16,173 $9,251
121,619
kWh
$3,075
-
kW-mo/yr
$5,392 $26,400
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs