| Assessment Year | 2003 |
|---|---|
| Principal Product | Turkey Products |
| NAICS | 311615: Poultry Processing |
| SIC | 2015: Poultry Slaughtering and Processing |
| Sales Range | $10 M to 50M |
| # of Employees | 100 |
| Plant Area |
52,000
ft2
|
| Annual Production | 600,000
pieces
|
| Production Hrs. Annual | 4,250
hrs
|
| Location (State) | New York |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $148,423 | 2,168,854 |
kWh
|
$0.068 |
| Electricity Demand | $76,685 | 6,089 |
kW-mo/yr
|
$12.59 |
| Electricity Fees | $10,972 | - |
|
- |
| Fuel Oil #2 | $48,219 | 6,491 |
MMBtu
|
$7.43 |
| Other Gas | $9,782 | 1,253 |
MMBtu
|
$7.81 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $330,823 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $151,457 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Fuel Oil #2 Savings | Other Gas Savings | Personnel Changes Savings |
|---|---|---|---|---|---|---|---|---|---|---|
| 01 | 2.9121: Install wind powered electric generator | $141,258 | $1,171,875 |
$64,081
2,096,364
kWh
|
$77,177
-
kW-mo/yr
|
- | - | - | - | |
| 02 | 2.2515: Use optimum thickness insulation | $115,419 | $348,540 | - | - | - | - |
$115,419
-
MMBtu
|
- | |
| 03 | 2.2628: Utilize a less expensive cooling method | $30,000 | $76,518 | - | - | - | - | - | $30,000 | |
| 04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $13,096 | $55,580 |
$13,096
230,256
kWh
|
- | - | - | - | - | |
| 05 | 2.6121: Reduce hot water temperature to the minimum required | $8,721 | - | - | - | - |
$8,721
-
MMBtu
|
- | - | |
| 06 | 2.9121: Install wind powered electric generator | $7,910 | $10,000 |
$2,606
37,225
kWh
|
$914
-
kW-mo/yr
|
$4,390 | - | - | - | |
| 07 | 2.5194: Redesign process | $6,861 | $270 |
$4,444
63,491
kWh
|
$2,417
-
kW-mo/yr
|
- | - | - | - | |
| 08 | 2.1233: Analyze flue gas for proper air/fuel ratio | $3,485 | $700 | - | - | - |
$3,485
-
MMBtu
|
- | - | |
| 09 | 2.2121: Increase amount of condensate returned | $1,293 | $955 | - | - | - |
$1,293
-
MMBtu
|
- | - | |
| 10 | 2.7491: Insulate glazing, walls, ceilings, and roofs | $847 | $1,744 |
$619
8,844
kWh
|
$228
-
kW-mo/yr
|
- | - | - | - | |
| 11 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $723 | $608 |
$530
7,570
kWh
|
$193
-
kW-mo/yr
|
- | - | - | - | |
| 12 | 2.6218: Turn off equipment when not in use | $550 | - |
$440
6,290
kWh
|
$110
-
kW-mo/yr
|
- | - | - | - | |
| 13 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $462 | $29 |
$462
6,605
kWh
|
- | - | - | - | - | |
| 14 | 2.4221: Install compressor air intakes in coolest locations | $198 | $150 |
$124
1,772
kWh
|
$74
-
kW-mo/yr
|
- | - | - | - | |
| TOTAL RECOMMENDED | $330,823 | $1,666,969 |
$86,402
2,458,417
kWh
|
$81,113
-
kW-mo/yr
|
$4,390 |
$13,499
-
MMBtu
|
$115,419
-
MMBtu
|
$30,000 | ||
| TOTAL IMPLEMENTED | $151,457 | $408,426 |
$19,591
323,056
kWh
|
$2,948
-
kW-mo/yr
|
- |
$13,499
-
MMBtu
|
$115,419
-
MMBtu
|
- | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Fuel Oil #2 Savings | Other Gas Savings | Personnel Changes Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs