| Assessment Year | 2002 |
|---|---|
| Principal Product | Creped tissue, Napkins and Waddings |
| NAICS |
n/a
|
| SIC | 2621: Paper Mills |
| Sales Range | $10 M to 50M |
| # of Employees | 120 |
| Plant Area |
125,000
ft2
|
| Annual Production | 30,000
ton
|
| Production Hrs. Annual | 8,712
hrs
|
| Location (State) | New York |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $1,484,723 | 30,166,629 |
kWh
|
$0.049 |
| Electricity Fees | $419,534 | - |
|
- |
| Natural Gas | $2,245,149 | 426,375 |
MMBtu
|
$5.27 |
| Fuel Oil #2 | $118,966 | - |
|
- |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $1,256,918 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $100,667 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings | Administrative Changes Savings | Increase in Production Savings |
|---|---|---|---|---|---|---|---|---|
| 01 | 2.3415: Use a fossil fuel engine to cogenerate electricity or motive power; and utilize heat | $593,735 | $5,128,500 |
$1,403,455
28,965,768
kWh
|
$(-664,891.0)
-
MMBtu
|
$(-144,829.0) | - | |
| 02 | 4.114: Add/modify equipment to improve drying process | $392,475 | $730,000 | - | - | - | $392,475 | |
| 03 | 2.2414: Use waste heat from hot flue gases to preheat | $147,968 | $19,500 | - |
$147,968
-
MMBtu
|
- | - | |
| 04 | 2.4133: Use most efficient type of electric motors | $35,283 | $64,018 |
$35,283
720,070
kWh
|
- | - | - | |
| 05 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $34,631 | $14,250 |
$34,631
706,750
kWh
|
- | - | - | |
| 06 | 2.1233: Analyze flue gas for proper air/fuel ratio | $25,122 | $700 | - |
$25,122
-
MMBtu
|
- | - | |
| 07 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $21,142 | $360 |
$21,142
431,466
kWh
|
- | - | - | |
| 08 | 2.2136: Install / repair insulation on steam lines | $3,151 | $8,733 | - |
$3,151
-
MMBtu
|
- | - | |
| 09 | 2.7111: Reduce illumination to minimum necessary levels | $2,480 | - |
$2,480
50,616
kWh
|
- | - | - | |
| 10 | 2.4239: Eliminate or reduce compressed air usage | $931 | $581 |
$931
19,000
kWh
|
- | - | - | |
| TOTAL RECOMMENDED | $1,256,918 | $5,966,642 |
$1,497,922
30,893,670
kWh
|
$(-488,650.0)
-
MMBtu
|
$(-144,829.0) | $392,475 | ||
| TOTAL IMPLEMENTED | $100,667 | $87,701 |
$72,394
1,477,436
kWh
|
$28,273
-
MMBtu
|
- | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings | Administrative Changes Savings | Increase in Production Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs