Assessment Year | 2001 |
---|---|
Principal Product | solid state controls |
NAICS |
n/a
|
SIC | 3625: Relays and Industrial Controls |
Sales Range | $10 M to 50M |
# of Employees | 220 |
Plant Area |
31,000
ft2
|
Annual Production | 2,313,321
pieces
|
Production Hrs. Annual | 6,240
hrs
|
Location (State) | New York |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $129,581 | 2,194,240 |
kWh
|
$0.059 |
Electricity Demand | $84,753 | 6,566 |
kW-mo/yr
|
$12.91 |
Electricity Fees | $10,481 | - |
|
- |
Natural Gas | $18,707 | 2,521 |
MMBtu
|
$7.42 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $34,681 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $2,144 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Water Disposal Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.7111: Reduce illumination to minimum necessary levels | $3,637 | - |
$2,522
42,048
kWh
|
$1,115
-
kW-mo/yr
|
- | - | |
02 | 2.3415: Use a fossil fuel engine to cogenerate electricity or motive power; and utilize heat | $27,282 | $372,500 |
$65,580
907,104
kWh
|
$30,915
-
kW-mo/yr
|
$(-69,213.0)
-
MMBtu
|
- | |
03 | 2.4231: Reduce the pressure of compressed air to the minimum required | $1,563 | - |
$1,563
26,057
kWh
|
- | - | - | |
04 | 2.2511: Insulate bare equipment | $55 | $45 |
$55
457
kWh
|
- | - | - | |
05 | 3.4111: Use closed cycle process to minimize waste water production | $2,144 | $9,900 | - | - | - |
$2,144
-
Tgal
|
|
TOTAL RECOMMENDED | $34,681 | $382,445 |
$69,720
975,666
kWh
|
$32,030
-
kW-mo/yr
|
$(-69,213.0)
-
MMBtu
|
$2,144
-
Tgal
|
||
TOTAL IMPLEMENTED | $2,144 | $9,900 | - | - | - |
$2,144
-
Tgal
|
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs