| Assessment Year | 1986 |
|---|---|
| Principal Product | CHINA & POTTERY |
| NAICS |
n/a
|
| SIC | 3262: Vitreous China Table and Kitchen Articles |
| Sales Range | $10 M to 50M |
| # of Employees | 400 |
| Plant Area |
n/a
|
| Annual Production | 400,000
pieces
|
| Production Hrs. Annual | 4,125
hrs
|
| Location (State) | New York |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $485,311 | 8,347,890 |
kWh
|
$0.058 |
| Natural Gas | $893,001 | 172,898 |
MMBtu
|
$5.16 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $146,596 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $133,150 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings |
|---|---|---|---|---|---|---|
| 01 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $6,553 | - |
$6,553
112,837
kWh
|
- | |
| 02 | 2.2437: Recover waste heat from equipment | $10,364 | $6,000 | - |
$10,364
-
MMBtu
|
|
| 03 | 2.2515: Use optimum thickness insulation | $1,489 | $1,500 | - |
$1,489
-
MMBtu
|
|
| 04 | 2.4133: Use most efficient type of electric motors | $1,008 | $3,000 |
$1,008
17,292
kWh
|
- | |
| 05 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $2,074 | $1,050 |
$2,074
35,756
kWh
|
- | |
| 06 | 2.2414: Use waste heat from hot flue gases to preheat | $125,108 | $160,000 | - |
$125,108
-
MMBtu
|
|
| TOTAL RECOMMENDED | $146,596 | $171,550 |
$9,635
165,885
kWh
|
$136,961
-
MMBtu
|
||
| TOTAL IMPLEMENTED | $133,150 | $161,500 |
$6,553
112,837
kWh
|
$126,597
-
MMBtu
|
||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs