Assessment Year | 2024 |
---|---|
Principal Product | Manufacturing Aerospace, Defense, Semiconductor |
NAICS | 332811: Metal Heat Treating |
SIC | 3398: Metal Heat Treating |
Sales Range | $10 M to 50M |
# of Employees | 31 |
Plant Area |
19,000
ft2
|
Annual Production | 30,000
units
|
Production Hrs. Annual | 2,600
hrs
|
Location (State) | California |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $78,995 | 387,184 |
kWh
|
$0.20 |
Electricity Demand | $23,543 | 1,282 |
kW-mo/yr
|
$18.36 |
Natural Gas | $17,562 | 640 |
MMBtu
|
$27.44 |
TOTAL YEARLY COSTS | $120,100 | |||
RECOMMENDED SAVINGS* | $60,280 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings |
---|---|---|---|---|---|---|
01 | 2.9114: Use solar heat to make electricty | $45,462 | $42,170 |
$43,180
211,668
kWh
|
$2,282
-
kW-mo/yr
|
|
02 | 2.3141: Use battery storage for demand control | $3,606 | $5,559 |
$1,570
7,695
kWh
|
$2,036
-
kW-mo/yr
|
|
03 | 2.4231: Reduce the pressure of compressed air to the minimum required | $490 | - |
$490
2,404
kWh
|
- | |
04 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $8,182 | - |
$8,182
40,107
kWh
|
- | |
05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,292 | $8,243 |
$1,029
5,042
kWh
|
$263
-
kW-mo/yr
|
|
06 | 2.6218: Turn off equipment when not in use | $1,248 | - |
$1,248
6,118
kWh
|
- | |
TOTAL RECOMMENDED | $60,280 | $55,972 |
$55,699
273,034
kWh
|
$4,581
-
kW-mo/yr
|
||
TOTAL IMPLEMENTED | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs