Assessment Year | 2023 |
---|---|
Principal Product | Weldments for semiconductor industry |
NAICS | 334413: Semiconductor and Related Device Manufacturing |
SIC | 3674: Semiconductors and Related Devices |
Sales Range | $10 M to 50M |
# of Employees | 150 |
Plant Area |
44,365
ft2
|
Annual Production | 140,000
units
|
Production Hrs. Annual | 4,550
hrs
|
Location (State) | California |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $85,518 | 370,796 |
kWh
|
$0.23 |
Electricity Demand | $20,814 | 1,596 |
kW-mo/yr
|
$13.04 |
Natural Gas | $12,690 | 587 |
MMBtu
|
$21.62 |
TOTAL YEARLY COSTS | $119,022 | |||
RECOMMENDED SAVINGS* | $95,681 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $9,836 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|
01 | 2.9114: Use solar heat to make electricty | $67,746 | $441,525 |
$65,883
285,203
kWh
|
$1,863
-
kW-mo/yr
|
- | |
02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $15,869 | $18,228 |
$13,631
59,103
kWh
|
$2,238
-
kW-mo/yr
|
- | |
03 | 2.7135: Install occupancy sensors | $1,699 | $844 |
$1,699
7,366
kWh
|
- | - | |
04 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $764 | $32 |
$764
3,311
kWh
|
- | - | |
05 | 2.7221: Lower temperature during the winter season and vice-versa | $6,705 | - | - | - |
$6,705
-
MMBtu
|
|
06 | 2.4231: Reduce the pressure of compressed air to the minimum required | $469 | - |
$469
2,032
kWh
|
- | - | |
07 | 2.2511: Insulate bare equipment | $8 | $200 |
$8
33
kWh
|
- | - | |
08 | 2.4133: Use most efficient type of electric motors | $513 | $624 |
$476
2,065
kWh
|
$37
-
kW-mo/yr
|
- | |
09 | 2.6212: Turn off equipment during breaks, reduce operating time | $1,761 | $2,675 |
$1,761
7,635
kWh
|
- | - | |
10 | 2.6127: Maintain air filters by cleaning or replacement | $147 | $50 |
$147
636
kWh
|
- | - | |
TOTAL RECOMMENDED | $95,681 | $464,178 |
$84,838
367,384
kWh
|
$4,138
-
kW-mo/yr
|
$6,705
-
MMBtu
|
||
TOTAL IMPLEMENTED | $9,836 | $1,750 |
$3,094
13,411
kWh
|
$37
-
kW-mo/yr
|
$6,705
-
MMBtu
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs