Assessment Year | 2023 |
---|---|
Principal Product | injection molded plastic parts for molecular diagnostics |
NAICS | 326199: All Other Plastics Product Manufacturing |
SIC | 3089: Plastics Products, Not Elsewhere Classified |
Sales Range | $50 M to 100M |
# of Employees | 400 |
Plant Area |
71,515
ft2
|
Annual Production | 225,265,000
units
|
Production Hrs. Annual | 8,760
hrs
|
Location (State) | California |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $1,331,859 | 10,552,767 |
kWh
|
$0.13 |
Electricity Demand | $186,162 | 18,080 |
kW-mo/yr
|
$10.30 |
Natural Gas | $21,124 | 1,019 |
MMBtu
|
$20.74 |
TOTAL YEARLY COSTS | $1,539,145 | |||
RECOMMENDED SAVINGS* | $229,882 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|
01 | 2.9114: Use solar heat to make electricty | $128,947 | $765,487 |
$126,596
1,003,061
kWh
|
$2,351
-
kW-mo/yr
|
- | |
02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $14,271 | $13,090 |
$12,836
101,704
kWh
|
$1,435
-
kW-mo/yr
|
- | |
03 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $951 | $495 |
$951
7,534
kWh
|
- | - | |
04 | 2.6218: Turn off equipment when not in use | $192 | - |
$173
1,369
kWh
|
$19
-
kW-mo/yr
|
- | |
05 | 2.7221: Lower temperature during the winter season and vice-versa | $1,529 | - |
$382
3,024
kWh
|
- |
$1,147
-
MMBtu
|
|
06 | 2.2621: Modify refrigeration system to operate at a lower pressure | $31,866 | $36,311 |
$31,866
252,481
kWh
|
- | - | |
07 | 2.4239: Eliminate or reduce compressed air usage | $47,492 | - |
$44,036
348,916
kWh
|
$3,456
-
kW-mo/yr
|
- | |
08 | 2.4231: Reduce the pressure of compressed air to the minimum required | $4,635 | - |
$4,635
36,722
kWh
|
- | - | |
TOTAL RECOMMENDED | $229,882 | $815,383 |
$221,474
1,754,811
kWh
|
$7,261
-
kW-mo/yr
|
$1,147
-
MMBtu
|
||
TOTAL IMPLEMENTED | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs