Assessment Year | 2024 |
---|---|
Principal Product | Recycled Plastic Pellets |
NAICS | 326199: All Other Plastics Product Manufacturing |
SIC | 3089: Plastics Products, Not Elsewhere Classified |
Sales Range | $1 M to 5M |
# of Employees | 23 |
Plant Area |
53,060
ft2
|
Annual Production | 10,000,000
lb
|
Production Hrs. Annual | 5,850
hrs
|
Location (State) | California |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | ||
---|---|---|---|---|---|
Electricity Usage | $321,419 | 2,231,677 |
kWh
|
$0.14 | |
Electricity Demand | $72,715 | 7,432 |
kW-mo/yr
|
$9.78 | |
Electricity Fees | $4,266 | - |
|
- | |
Waste Disposal Costs | |||||
Water Usage | $1,362 | 73,316 |
Tgal
|
$0.019 | |
Water Disposal | $4,157 | 73,316 |
Tgal
|
$0.057 | |
TOTAL YEARLY COSTS | $403,919 | ||||
RECOMMENDED SAVINGS* | $147,966 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Personnel Changes Savings | Primary Product Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.6218: Turn off equipment when not in use | $1,603 | - |
$1,603
10,984
kWh
|
- | - | - | |
02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,414 | $1,073 |
$1,233
8,447
kWh
|
$169
-
kW-mo/yr
|
$43 | $(-31.0) | |
03 | 2.7134: Use photocell controls | $509 | $718 |
$339
2,323
kWh
|
- | $13 | $157 | |
04 | 2.2614: Use cooling tower or economizer to replace chiller cooling | $14,370 | $58,959 |
$14,370
98,490
kWh
|
- | - | - | |
05 | 2.9114: Use solar heat to make electricty | $130,070 | $760,719 |
$130,070
891,502
kWh
|
- | - | - | |
TOTAL RECOMMENDED | $147,966 | $821,469 |
$147,615
1,011,746
kWh
|
$169
-
kW-mo/yr
|
$56 | $126 | ||
TOTAL IMPLEMENTED | - | - | - | - | - | - |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs